Parameters
FC
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
18
19
20
27
29
32
33
31
50
53
54
55
42
130BD069.11
45
A OUT
Function
Setting
5-10 Terminal 18
Digital Input
[8] Start*
5-12 Terminal 27
Digital Input
[19] Freeze
Reference
5-13 Terminal 29
Digital Input
[21] Speed
Up
5-14 Terminal 32
Digital Input
[22] Speed
Down
* = Default value
Notes/comments:
Table 6.8 Speed Up/Down
Start (18)
Freeze ref (27)
Speed up (29 )
Speed down (32 )
Speed
Reference
130BB840.11
Illustration 6.1 Speed Up/Down
CAUTION
Thermistors must use reinforced or double insulation to
meet PELV insulation requirements.
Parameters
130BD070.11
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
18
19
20
27
29
32
33
31
50
53
54
55
42
FC
45
A OUT
Function
Setting
1-90 Motor
Thermal
Protection
[2]
Thermistor
trip
1-93 Thermistor
Source
[1] Analog
input 53
6-19 Terminal 53
mode
[1] Voltage
* = Default value
Notes/comments:
If only a warning is desired,
1-90 Motor Thermal Protection
should be set to
[1] Thermistor
warning
.
Table 6.9 Motor Thermistor
Application Examples
Design Guide
80
Danfoss A/S © 09/2014 All rights reserved.
MG06B402