Terminal
Parameter
Default
setting
Description
50
–
+10 V DC
10 V DC analog
supply voltage.
15 mA
maximum
commonly used
for potenti-
ometer or
thermistor.
53
6-1* parameter
group
Reference
Analog input.
Selectable for
voltage or
current.
54
6-2* parameter
group
Feedback
55
–
Common for
analog input
Serial communication
61
–
Integrated RC-
Filter for cable
screen. ONLY for
connecting the
screen when
experiencing
EMC problems.
68 (+)
8-3* parameter
group
RS485 interface.
A control card
switch is
provided for
termination
resistance.
69 (-)
8-3* parameter
group
Relays
01, 02, 03
5-40 [0]
[0] No
operation
Form C relay
output. These
relays are in
various locations
depending upon
the frequency
converter config-
uration and size.
Usable for AC or
DC voltage and
resistive or
inductive loads.
RO2 in J1–J3
enclosure is 2-
pole, only
terminals 04 and
05 are available
04, 05, 06
5-40 [1]
[0] No
operation
Table 2.2 Terminal Descriptions
Control terminal functions
Frequency converter functions are commanded by
receiving control input signals.
•
Programme each terminal for the function it
supports in the parameters associated with that
terminal.
•
Confirm that the control terminal is programmed
for the correct function. See
chapter Local Control
Panel and Programming
in the quick guide for
details on accessing parameters and
programming.
•
The default terminal programming initiates
frequency converter functioning in a typical
operational mode.
Using screened control cables
The preferred method in most cases is to secure control
and serial communication cables with screening clamps
provided at both ends to ensure the best possible high
frequency cable contact.
If the ground potential between the frequency converter
and the PLC is different, electric noise may occur that
disturbs the entire system. Solve this problem by fitting an
equalising cable as close as possible to the control cable.
Minimum cable cross section: 16 mm
2
(6 AWG).
1
2
PE
FC
PE
PLC
130BB922.12
PE
PE
<10 mm
1
Minimum 16 mm
2
(6 AWG)
2
Equalising cable
Illustration 2.8 Screening Clamps at Both Ends
50/60 Hz ground loops
With very long control cables, ground loops may occur. To
eliminate ground loops, connect one end of the screen-to-
ground with a 100 nF capacitor (keeping leads short).
100nF
FC
PE
PE
PLC
<10 mm
130BB609.12
Illustration 2.9 Connection with a 100 nF Capacitor
Product Overview
Design Guide
MG06B402
Danfoss A/S © 09/2014 All rights reserved.