2.2.4 Control Wiring
Access
•
Remove the cover plate with a screwdriver. See
130BC504.10
Illustration 2.6 Control Wiring Access for Enclosure Sizes J1–J7
Control Terminal Types
shows the frequency converter control
terminals. Terminal functions and default settings are
summarised in
.
42 45
12
18
19
27
29
31
32
33
20
50
53
54
55
130BC505.12
Illustration 2.7 Control Terminal Locations
See
chapter 4.2 General Specifications
for terminal ratings
details.
Terminal
Parameter
Default
setting
Description
Digital I/O, Pulse I/O, Encoder
12
–
+24 V DC
24 V DC supply
voltage.
Maximum
output current is
100 mA for all
24 V loads.
18
5-10 Terminal 18
Digital Input
[8] Start
Digital inputs.
19
5-11 Terminal 19
Digital Input
[10]
Reversing
31
5-16 Terminal 31
Digital Input
[0] No
operation
Digital input
32
5-14 Terminal 32
Digital Input
[0] No
operation
Digital input, 24
V encoder.
Terminal 33 can
be used for
pulse input.
33
5-15 Terminal 33
Digital Input
[0] No
operation
27
5-12 Terminal 27
Digital Input
5-30 Terminal 27
Digital Output
DI [2] Coast
inverse
DO [0] No
operation
Selectable for
either digital
input, digital
output or pulse
output. Default
setting is digital
input.
Terminal 29 can
be used for
pulse input.
29
5-13 Terminal 29
Digital Input
5-31 Terminal 29
Digital Output
DI [14] Jog
DO [0] No
operation
20
–
Common for
digital inputs
and 0 V
potential for 24
V supply.
Analog inputs/outputs
42
6-91 Terminal 42
Analog Output
[0] No
operation
Programmable
analog output.
The analog
signal is 0–20
mA or 4–20 mA
at a maximum
of 500
Ω
. Can
also be
configured as
digital outputs
45
6-71 Terminal 45
Analog Output
[0] No
operation
Product Overview
Design Guide
16