Parameters
130BD067.11
FC
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
18
19
20
27
29
32
33
31
50
53
54
55
42
45
A OUT
Function
Setting
5-11 Terminal 19
Digital Input
[1] Reset
* = Default value
Notes/comments:
Table 6.5 External Alarm Reset
Parameters
130BB068.11
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
18
19
20
27
29
32
33
31
50
53
54
55
42
≈ 5kΩ
FC
45
A OUT
Function
Setting
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal 53
High Voltage
10 V*
6-14 Terminal 53
Low Ref./Feedb.
Value
0
6-15 Terminal 53
High Ref./Feedb.
Value
1500
6-19 Terminal 53
mode
[1] voltage
* = Default value
Notes/comments:
Table 6.6 Speed Reference (Using a Manual Potentiometer)
Parameters
FC
+24 V
D IN
D IN
COM
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
R1
R2
12
18
19
20
27
29
32
33
31
50
53
54
55
42
01
02
03
04
05
06
130BD150.11
45
A OUT
Function
Setting
4-30 Motor
Feedback Loss
Function
[1] Warning
4-31 Motor
Feedback Speed
Error
100
4-32 Motor
Feedback Loss
Timeout
5 s
7-00 Speed PID
Feedback Source
[2] MCB 102
17-11 Resolution
(PPR)
1024*
13-00 SL
Controller Mode
[1] On
13-01 Start Event
[19] Warning
13-02 Stop Event
[44] Reset
key
13-10 Comparato
r Operand
[21] Warning
no.
13-11 Comparato
r Operator
[1] ≈*
13-12 Comparato
r Value
90
13-51 SL
Controller Event
[22]
Comparator 0
13-52 SL
Controller Action
[32] Set
digital out A
low
5-40 Function
Relay
[80] SL digital
output A
* = Default value
Notes/comments:
If the limit in the feedback
monitor is exceeded, warning
90 is issued. The SLC monitors
warning 90. If warning 90
becomes
true
, relay 1 is
triggered.
External equipment may then
indicate that service is required.
If the feedback error goes
below the limit again within 5
s, the frequency converter
continues and the warning
disappears. But relay 1 persists
until [Off/Reset] is pressed.
Table 6.7 Using SLC to Set a Relay
Application Examples
Design Guide
MG06B402