3.3 Ordering Numbers: Brake Resistors
Danfoss offers a wide variety of different resistors that are specially designed to our frequency converters. See
chapter 2.9.4 Control with Brake Function
for the dimensioning of brake resistors. This section lists the ordering numbers for
the brake resistors.
3.3.1 Ordering Numbers: Brake Resistors 10%
FC 360
P
m (HO)
R
min
R
br. nom
R
rec
P
br avg
Code no.
Period
Cable
cross
section
1)
Thermalr
elay
Maximu
m brake
torque
with R
rec
T4
[kW]
[
Ω
]
[
Ω
]
[
Ω
]
[kW]
175Uxxxx
[s]
[mm
2
]
[A]
[%]
HK37
0.37
890
1041.98
989
0.030
3000
120
1.5
0.3
139
HK55
0.55
593
693.79
659
0.045
3001
120
1.5
0.4
131
HK75
0.75
434
508.78
483
0.061
3002
120
1.5
0.4
129
H1K1
1.1
288
338.05
321
0.092
3004
120
1.5
0.5
132
H1K5
1.5
208
244.41
232
0.128
3007
120
1.5
0.8
145
H2K2
2.2
139
163.95
155
0.190
3008
120
1.5
0.9
131
H3K0
3
100
118.86
112
0.262
3300
120
1.5
1.3
131
H4K0
4
74
87.93
83
0.354
3335
120
1.5
1.9
128
H5K5
5.5
54
63.33
60
0.492
3336
120
1.5
2.5
127
H7K5
7.5
38
46.05
43
0.677
3337
120
1.5
3.3
132
H11K
11
27
32.99
31
0.945
3338
120
1.5
5.2
130
H15K
15
19
24.02
22
1.297
3339
120
1.5
6.7
129
H18K
18.5
16
19.36
18
1.610
3340
120
1.5
8.3
132
H22K
22
16
18.00
17
1.923
3357
120
1.5
10.1
128
H30K
30
11
14.6
13
2.6
3341
120
2.5
13.3
150
H37K
37
9
11.7
11
3.2
3359
120
2.5
15.3
150
H45K
45
8
9.6
9
3.9
3065
120
10
20
150
H55K
55
6
7.8
7
4.8
3070
120
10
26
150
H75K
75
4
5.7
5
6.6
3231
120
10
36
150
Table 3.2 FC 360 - Mains: 380–480 V (T4), 10% Duty Cycle
1) All cabling must comply with national and local regulations on cable cross-sections and ambient temperature.
Type Code and Selection
Design Guide
48
Danfoss A/S © 09/2014 All rights reserved.
MG06B402
3
3