Function
Parameter
number
Setting
Initialise the frequency converter
14-22
[2] Initialisation - make a power cycling - press reset
1) Set motor parameters:
Set the motor parameters according to name plate
data
1-2*
As stated on motor name plate
Perform a full Automation Motor Adaptation
1-29
[1] Enable complete AMA
2) Check that motor is running in the correct direction.
When the motor is connected to the frequency converter with straight forward phase order as U-U; V-V; W-W, the motor shaft usually
turns clockwise seen into shaft end.
Press [Hand On]. Check the shaft direction by
applying a manual reference.
If the motor turns opposite of required direction:
1. Change motor direction in
4-10 Motor Speed
Direction
.
2. Turn off mains, and wait for DC link to
discharge.
3. Switch 2 of the motor phases.
4-10
Select correct motor shaft direction
Set configuration mode
1-00
[3] Process
3) Set reference configuration, ie. the range for reference handling. Set scaling of analog input in parameter 6-**
Set reference/feedback units
Set minimum reference (10
°
C)
Set maximum reference (80
°
C)
If the set value is determined from a preset value
(array parameter), set other reference sources to
No Function
3-01
3-02
3-03
3-10
[60]
°
C Unit shown on display
-5
°
C
35
°
C
[0] 35%
Ref
=
Par
. 3
−
10 0
100
×
Par
. 3
−
03
−
par
. 3
−
02 = 24,5°
C
3-14 Preset Relative Reference
to
3-18 Relative Scaling Reference
Resource
[0] = No Function
4) Adjust limits for the frequency converter:
Set ramp times to an appropriate value as 20 s
3-41
3-42
20 s
20 s
Set minimum speed limits
Set motor speed maximum limit
Set maximum output frequency
4-12
4-14
4-19
10 Hz
50 Hz
60 Hz
Set
6-19 Terminal 53 mode
and
6-29 Terminal 54 mode
to voltage or current mode.
5) Scale analog inputs used for reference and feedback
Set terminal 53 low voltage
Set terminal 53 high voltage
Set terminal 54 low feedback value
Set terminal 54 high feedback value
Set feedback source
6-10
6-11
6-24
6-25
7-20
0 V
10 V
-5
°
C
35
°
C
[2] Analog input 54
6) Basic PID settings
Process PID normal/inverse
7-30
[0] Normal
Process PID anti wind-up
7-31
[1] On
Process PID start speed
7-32
300 RPM
Save parameters to LCP
0-50
[1] All to LCP
Table 2.9 Example of Process PID Control Set-up