7-06 Speed PID Lowpass Filter Time
Range:
Function:
Application
dependent
*
[1.0 -
100.0
ms]
Set a time constant for the speed control
low-pass filter. The low-pass filter
improves steady-state performance and
dampens oscillations on the feedback
signal. This is an advantage if there is a
great amount on noise in the system, see
illustration below. For example, if a time
constant (τ) of 100 ms is programmed, the
cut-off frequency for the low-pass filter
will be 1/0.1= 10 RAD/sec., corresponding
to (10/2 x π) = 1.6 Hz. The PID regulator
only regulates a feedback signal that
varies by a frequency of less than 1.6 Hz. If
the feedback signal varies by a higher
frequency than 1.6 Hz, the PID regulator
does not react.
Practical settings of
taken from the number
of pulses per revolutions from encoder:
Encoder PPR
7-06 Speed PID
Lowpass Filter Time
512
10 ms
1024
5 ms
2048
2 ms
4096
1 ms
Note that severe filtering can be
detrimental to dynamic performance.
This parameter is used with
Speed closed loop
[1] and
Torque
[2] control.
The filter time in flux sensorless must be
adjusted to 3-5 ms.
0.6
0.6
f
g
= 10 Hz
175ZA293.11
Feedback
Disturbed feedback signal
t (Sec.)
t (Sec.)
Filtered feedback signal
Lowpass filter
Feedback
Parameter Descriptions
FC 300 Programming Guide
98
MG.33.MB.02 - VLT
®
is a registered Danfoss trademark
3
3