5-19 Terminal 37 Safe Stop
Option:
Function:
[1]
*
Safe Stop
Alarm
Coasts frequency converter when safe stop is
activated. Manual reset from LCP, digital input
or fieldbus.
[3]
Safe Stop
Warning
Coasts frequency converter when safe stop is
activated (T-37 off). When safe stop circuit is
reestablished, the frequency converter will
continue without manual reset.
[4]
PTC 1 Alarm Coasts frequency converter when safe stop is
activated. Manual reset from LCP, digital input
or fieldbus. Choice 4 is only available when the
MCB 112 PTC Thermistor Card is connected.
[5]
PTC 1
Warning
Coasts frequency converter when safe stop is
activated (T-37 off). When safe stop circuit is
reestablished, the frequency converter will
continue without manual reset, unless a Digital
Input set to PTC Card 1 [80] is still enabled.
Choice 5 is only available when the MCB 112
PTC Thermistor Card is connected.
[6]
PTC 1 &
Relay A
This choice is used when the PTC option is
gated together with a Stop button through a
Safety relay to T-37. Coasts frequency converter
when safe stop is activated. Manual reset from
LCP, digital input or fieldbus. Choice 6 is only
available when the MCB 112 PTC Thermistor
Card is connected.
[7]
PTC 1 &
Relay W
This choice is used when the PTC option is
gated together with a Stop button through a
Safety relay to T-37. Coasts frequency converter
when safe stop is activated (T-37 off). When
safe stop circuit is reestablished, the frequency
converter will continue without manual reset,
unless a Digital Input set to PTC Card 1 [80] is
(still) enabled. Choice 7 is only available when
the MCB 112 PTC Thermistor Card is connected.
[8]
PTC 1 &
Relay A/W
This choice makes it possible to use a
combination of Alarm and Warning. Choice 8 is
only available when the MCB 112 PTC
Thermistor Card is connected.
[9]
PTC 1 &
Relay W/A
This choice makes it possible to use a
combination of Alarm and Warning. Choice 9 is
only available when the MCB 112 PTC
Thermistor Card is connected.
Choises 4 - 9 are only available when the MCB 112 PTC
Thermistor Card is connected.
NOTE
When Auto Reset/Warning is selected the frequency
converter opens up for automatic restart.
Overview of functions, alarms and warnings
Function
No.
PTC
Relay
No Function
[0]
-
-
Safe Stop Alarm
[1]*
-
Safe Stop [A68]
Safe Stop Warning
[3]
-
Safe Stop [W68]
PTC 1 Alarm
[4]
PTC 1 Safe Stop
[A71]
-
PTC 1 Warning
[5]
PTC 1 Safe Stop
[W71]
-
PTC 1 & Relay A
[6]
PTC 1 Safe Stop
[A71]
Safe Stop [A68]
PTC 1 & Relay W
[7]
PTC 1 Safe Stop
[W71]
Safe Stop [W68]
PTC 1 & Relay A/W [8]
PTC 1 Safe Stop
[A71]
Safe Stop [W68]
PTC 1 & Relay W/A [9]
PTC 1 Safe Stop
[W71]
Safe Stop [A68]
W means warning and A means alarm. For further
information, see Alarms and Warnings in section
Trouble-
shooting
in the Design Guide or the Operating Instructions
A dangerous failure related to Safe Stop will give Alarm:
Dangerous Failure [A72].
Please refer to the section
Description of Alarm Word, Warning
Word and extended Status Word
in the chapter
Trouble-
shooting
.
5-20 Terminal X46/1 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB 113 is installed in the frequency
converter. Functions are described under 5-1*
Digital Inputs
5-21 Terminal X46/3 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option
moduleMCB 113 is installed in the frequency
converter. Functions are described under 5-1*
Digital Inputs
5-22 Terminal X46/5 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option
moduleMCB 113 is installed in the frequency
converter. Functions are described under 5-1*
Digital Inputs
5-23 Terminal X46/7 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option
moduleMCB 113 is installed in the frequency
converter. Functions are described under 5-1*
Digital Inputs
Parameter Descriptions
FC 300 Programming Guide
74
MG.33.MB.02 - VLT
®