9-47 Fault Number
Range:
Function:
0
*
[0 - 0 ] This buffer contains the alarm number (e.g. 2 for live
zero error, 4 for mains phase loss) for all alarms and
warnings that have occurred since last reset or
power-up. The maximum buffer capacity is eight
error events.
9-52 Fault Situation Counter
Range:
Function:
0
*
[0 - 1000 ] This parameter displays the number of error
events which have occurred since last reset of
power-up.
9-53 Profibus Warning Word
Range:
Function:
0
*
[0 - 65535 ] This parameter displays Profibus communi-
cation warnings. Please refer to the
Profibus
Operating Instructions
for further information.
Read only
Bit:
Meaning:
0
Connection with DP-master is not ok
1
Not used
2
FDLNDL (Fieldbus Data link Layer) is not ok
3
Clear data command received
4
Actual value is not updated
5
Baudrate search
6
PROFIBUS ASIC is not transmitting
7
Initialisation of PROFIBUS is not ok
8
Frequency converter is tripped
9
Internal CAN error
10
Wrong configuration data from PLC
11
Wrong ID sent by PLC
12
Internal error occured
13
Not configured
14
Timeout active
15
Warning 34 active
9-63 Actual Baud Rate
Option:
Function:
This parameter displays the actual
Profibus baud rate. The Profibus
Master automatically sets the baud
rate.
[0]
9,6 kbit/s
[1]
19,2 kbit/s
[2]
93,75 kbit/s
[3]
187,5 kbit/s
[4]
500 kbit/s
[6]
1500 kbit/s
[7]
3000 kbit/s
[8]
6000 kbit/s
9-63 Actual Baud Rate
Option:
Function:
[9]
12000 kbit/s
[10]
31,25 kbit/s
[11]
45,45 kbit/s
[255]
*
No baudrate found
9-64 Device Identification
Range:
Function:
0
*
[0 - 0 ] This parameter displays the device identification.
Please refer to the
Operating Instructions for Profibus,
MG.33.CX.YY for further explanation.
9-65 Profile Number
Range:
Function:
0
*
[0 - 0 ] This parameter contains the profile identification.
Byte 1 contains the profile number and byte 2 the
version number of the profile.
NOTE
This parameter is not visible via LCP.
9-67 Control Word 1
Range:
Function:
0
*
[0 - 65535 ] This parameter accepts the Control Word from a
Master Class 2 in the same format as PCD 1.
9-68 Status Word 1
Range:
Function:
0
*
[0 - 65535 ] This parameter delivers the Status Word for a
Master Class 2 in the same format as PCD 2.
9-70 Programming Set-up
Option:
Function:
Select the set-up to be edited.
[0]
Factory setup Uses default data. This option can be used as
a data source to return the other set-ups to a
known state.
[1]
Set-up 1
Edits Set-up 1.
[2]
Set-up 2
Edits Set-up 2.
[3]
Set-up 3
Edits Set-up 3.
[4]
Set-up 4
Edits Set-up 4.
[9]
*
Active Set-up Follows the active set-up selected in
0-10 Active Set-up
.
This parameter is unique to LCP and fieldbuses. See also
0-11 Programming Set-up
.
Parameter Descriptions
FC 300 Programming Guide
114
MG.33.MB.02 - VLT
®