1-72 Start Function
Option:
Function:
or
and the output
current corresponds to the setting of the start
current in
. This function is
typically used in hoisting applications without
counterweight and especially in applications
with a Cone-motor, where the start is
clockwise, followed by rotation in the
reference direction.
[4]
Horizontal
operation
Only possible with VVC
plus
.
For obtaining the function described in
and
during the start delay time. The motor rotates
in the reference direction. If the reference
signal equals zero (0),
is
ignored and the output speed equals zero (0).
The output current corresponds to the setting
of the start current in
[5]
VVC+/Flux
clockwise
for the function described in
only. The start current is calculated
automatically. This function uses the start
speed in the start delay time only. Regardless
of the value set by the reference signal, the
output speed equals the setting of the start
speed in
Start speed/
current clockwise
[3] and
VVC
plus
/Flux clockwise
[5] are typically used in hoisting applications.
Start speed/current in reference direction
[4] is
particularly used in applications with counter-
weight and horizontal movement.
[6]
Hoist Mech.
Brake Rel
For utilizing mechanical brake control
functions,
to
. This parameter is only active when
is set to [3]
Flux w/
motor feedback (FC 302 only)
.
[7]
VVC+/Flux
counter-cw
1-73 Flying Start
Option:
Function:
This function makes it possible to catch a
motor which is spinning freely due to a
mains drop-out.
[0]
*
Disabled
No function
[1]
Enabled
Enables the frequency converter to
“catch” and control a spinning motor.
When
is enabled,
and
have no function.
[2]
Enabled Always
[3]
Enabled Ref. Dir.
[4]
Enab. Always Ref.
Dir.
This parameter cannot be adjusted while motor is running.
NOTE
This function is not recommended for hoisting applications.
For power levels above 55kW, flux mode must be used to
achieve the best performance.
NOTE
To obtain the best flying start performance the advanced
motor data, parameters 1-30 through 1-35, must be correct.
1-74 Start Speed [RPM]
Range:
Function:
Application
dependent
*
[0 - 600
RPM]
Set a motor start speed. After the
start signal, the output speed leaps
to set value. Set the start function in
to [3], [4] or [5],
and set a start delay time in
.
1-75 Start Speed [Hz]
Range:
Function:
Application
dependent
*
[Application
dependant]
This parameter can be used for
hoist applications (cone rotor). Set
a motor start speed. After the start
signal, the output speed leaps to
set value. Set the start function in
to [3], [4] or [5],
and set a start delay time in
1-76 Start Current
Range:
Function:
0.00
A
*
[Application
dependant]
Some motors, e.g. cone rotor motors,
need extra current/starting speed to
disengage the rotor. To obtain this boost,
set the required current in
. Set
. Set
to [3] or [4], and set a
start delay time in
.
This parameter can be used for hoist
applications (cone rotor).
3.3.8 1-8* Stop Adjustments
1-80 Function at Stop
Option:
Function:
Select the frequency converter function after
a stop command or after the speed is ramped
down to the settings in
.
[0]
*
Coast
Leaves motor in free mode. The motor is
disconnected from the frequency converter.
Parameter Descriptions
FC 300 Programming Guide
42
MG.33.MB.02 - VLT
®
is a registered Danfoss trademark