Line Power Supply 3 x 380–480 V AC
P160
P200
P250
Typical Shaft output at 400 V
[kW]
160
200
250
Typical Shaft output at 460 V
[HP]
250
300
350
Enclosure
IP21
D11
D11
D11
Enclosure IP54
D11
D11
D11
Output current
Continuous
(at 400 V) [A]
315
395
480
Intermittent (60 sec overload)
(at 400 V) [A]
347
435
528
Continuous
(at 460/ 480 V) [A]
302
361
443
Intermittent (60 sec overload)
(at 460/480 V) [A]
332
397
487
Continuous KVA
(at 400 V) [KVA]
218
274
333
Continuous KVA
(at 460 V) [KVA]
241
288
353
Max. input current
Continuous
(at 400 V) [A]
304
381
463
Continuous
(at 460/ 480 V) [A]
291
348
427
Max. cable size, line power mo-
tor, brake and load share [mm
2
(AWG
2)
)]
2 x 185
(2 x 300 mcm)
2 x 185
(2 x 300 mcm)
2 x 185
(2 x 300 mcm)
Max. external pre-fuses [A]
1
400
500
630
Estimated motor power loss
at rated max. load [W]
4)
, 400 V
4029
5130
5621
Estimated motor power loss
at rated max. load [W]
4)
, 460 V
3892
4646
5126
Estimated filter losses, 400 V
4954
5714
6234
Estimated filter losses, 460 V
5279
5819
6681
Weight,
enclosure IP21, IP 54 [kg]
380
380
406
Efficiency
4)
0.96
Output
frequency
0–800
Hz
Heatsink overtemp. trip
230°F [110
°
C]
230°F [110
°
C]
230°F [110
°
C]
Power card ambient trip
140°F [60
°
C]
VLT AQUA Low Harmonic Drive Instruction
Manual
8 General Specifications
MG.20.T1.22 - VLT
®
is a registered Danfoss trademark
8-5
8