Data transfer from LCP to adjustable frequency drive:
1.
Go to par. 0-50
LCP Copy
2.
Press the [OK] key
3.
Select “All from LCP”
4.
Press the [OK] key
The parameter settings stored in the GLCP are now transferred to the adjustable frequency drive indicated by the progress bar. When 100% is reached,
press [OK].
5.1.10 Initialization to Default Settings
There are two ways to initialize the adjustable frequency drive to default: Recommended initialization and manual initialization.
Please be aware that they have different impacts according to the below description.
Recommended initialization (via par. 14-22
Operation Mode
)
1.
Select par. 14-22
Operation Mode
2.
Press [OK]
3.
Select “Initialization” (for NLCP select “2”)
4.
Press [OK]
5.
Disconnect the power from the unit and wait for the display to
turn off.
6.
Reconnecting the power resets the adjustable frequency drive.
Note that first start-up takes a few more seconds
7.
Press [Reset]
Par. 14-22
Operation Mode
initializes all except:
Par. 14-50
RFI filter
Par. O-30
Protocol
Par. O-31
Address
Par. 8-32
FC Port Baud Rate
Par. 8-35
Minimum Response Delay
Par. O-36
Max Response Delay
Par. 8-37
Max Inter-Char Delay
Par. 15-00
Operating Hours
to par. 15-05
Overvolts
Par. 15-20
Historic Log: Event
to par. 15-22
Historic Log: Time
Par. 15-30
Fault Log: Error Code
to par. 15-32
Fault Log: Time
NOTE!
Parameters selected in par. 0-25
My Personal Menu
will remain present with the default factory setting.
Manual initialization
NOTE!
When carrying out manual initializationrestore, serial communication, RFI filter settings and fault log settings are reset.
Removes parameters selected in par. 0-25
My Personal Menu
.
1. Disconnect from the line power and wait until the display
turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while
powering up the Graphical LCP (GLCP)
2b. Press [Menu] while powering up for LCP 101, Numerical
Display
3. Release the keys after 5 s
4. The adjustable frequency drive is now programmed according
to default settings
This parameter initializes all except:
Par. 15-00
Operating Hours
Par. 15-03
Power-ups
Par. 15-04
Overtemps
Par. 15-05
Overvolts
VLT AQUA Low Harmonic Drive Instruction
Manual
5 How to Operate the Low Harmonic Drive
MG.20.T1.22 - VLT
®
is a registered Danfoss trademark
5-9