22-39 High Speed Power [HP]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-03
Regional Settings
has been set for North America (parameter not visible if
International selected).
Set power consumption to 85% speed level.
This function is used for storing values needed to tune No-flow Detection.
22-40 Minimum Run Time
Range:
Function:
10 s*
[0 - 600 s]
Set the desired minimum running time for the motor after a start command (digital input or bus)
before entering sleep mode.
22-41 Minimum Sleep Time
Range:
Function:
10 s*
[0 - 600 s]
Set the desired minimum time for staying in sleep mode. This will override any wake-up conditions.
22-42 Wake-up Speed [RPM]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-02
Motor Speed Unit
has been set for RPM (parameter not visible if Hz selected).
Only to be used if par. 1-00
is set for open-loop and speed reference is applied
by an external controller.
Set the reference speed at which sleep mode should be canceled.
22-43 Wake-up Speed [Hz]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-02
Motor Speed Unit
has been set for Hz (parameter not visible if RPM selected).
Only to be used if par. 1-00
is set for open-loop and speed reference is applied
by an external controller controlling the pressure.
Set the reference speed at which sleep mode should be canceled.
22-44 Wake-up Ref./FB Difference
Range:
Function:
10%*
[0-100%]
Only to be used if par. 1-00,
Configuration Mode
, is set for closed-loop and the integrated PI con-
troller is used for controlling the pressure.
Set the pressure drop allowed as a percentage of the setpoint for the pressure (Pset) before can-
celing sleep mode.
NOTE!
If used in application where the integrated PI controller is set for inverse control
in par. 20-71,
PID, Normal/Inverse Control
, the value set in par. 22-44 will au-
tomatically be added.