0-71 Date Format
Option:
Function:
[0] *
YYYY-MM-DD
Sets the date format to be used in the LCP.
[1]
DD-MM-YYYY
Sets the date format to be used in the LCP.
[2]
MM/DD/YYYY
Sets the date format to be used in the LCP.
0-72 Time Format
Option:
Function:
Sets the time format to be used in the LCP.
[0] *
24 h
[1]
12 h
0-74 DST/Summertime
Option:
Function:
Choose how Daylight Saving Time/Summertime should be handled. For manual DST/Summertime
enter the start date and end date in par. 0-76
[0] *
OFF
[2]
Manual
0-76 DST/Summertime Start
Range:
Function:
Application
dependent*
[Application dependant]
Sets the date and time when summertime/DST starts. The date is programmed in the format se-
lected in par. 0-71
Date Format
.
0-77 DST/Summertime End
Range:
Function:
Application
dependent*
[Application dependant]
Sets the date and time when summertime/DST ends. The date is programmed in the format selected
in par. 0-71
Date Format
.
6.3.3 General Settings, 1-0*
Define whether the adjustable frequency drive operates in open-loop or closed-loop.
1-00 Configuration Mode
Option:
Function:
[0] *
Open-loop
Motor speed is determined by applying a speed reference or by setting desired speed when in Hand
Mode.
Open-loop is also used if the adjustable frequency drive is part of a closed-loop control system based
on an external PID controller providing a speed reference signal as output.
[3]
Closed-loop
Motor speed will be determined by a reference from the built-in PID controller varying the motor
speed as part of a closed-loop control process (e.g., constant pressure or flow). The PID controller
must be configured in par. 20-** or via the function set-ups accessed by pressing the [Quick Menu]
button.