22-32 Low Speed [RPM]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-02
Motor Speed Unit
has been set for RPM (parameter not visible if Hz selected).
Set used speed to the 50% level.
This function is used for storing values needed to tune No-flow Detection.
22-33 Low Speed [Hz]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-02
Motor Speed Unit
has been set for Hz (parameter not visible if RPM selected).
Set used speed to the 50% level.
The function is used for storing values needed to tune No-flow Detection.
22-34 Low Speed Power [kW]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-03
Regional Settings
has been set for International (parameter not visible if
North America selected).
Set power consumption to 50% speed level.
This function is used for storing values needed to tune No-flow Detection.
22-35 Low Speed Power [HP]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-03
Regional Settings
has been set for North America (parameter not visible if
International selected).
Set power consumption to 50% speed level.
This function is used for storing values needed to tune No-flow Detection.
22-36 High Speed [RPM]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-02
Motor Speed Unit
has been set for RPM (parameter not visible if Hz selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No-flow Detection.
22-37 High Speed [Hz]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-02
Motor Speed Unit
has been set for Hz (parameter not visible if RPM selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No-flow Detection.
22-38 High Speed Power [kW]
Range:
Function:
Application
dependent*
[Application dependant]
To be used if par. 0-03
Regional Settings
has been set for International (parameter not visible if
North America selected).
Set power consumption to 85% speed level.
This function is used for storing values needed to tune No-flow Detection.
VLT AQUA Low Harmonic Drive Instruction
Manual
6 How to Program the Low Harmonic Drive
MG.20.T1.22 - VLT
®
is a registered Danfoss trademark
6-37
6