22-90 Flow at Rated Speed
Range:
Function:
0.000*
[0.000 - 999999.999 ]
Enter the value corresponding to Flow at Rated Speed. This value can be defined using the pump
datasheet.
6.3.11 23-0* Timed Actions
Use
Timed Actions
for actions needing to be performed on a daily or weekly basis, e.g., different references for working hours / non-working hours. Up
to 10 Timed Actions can be programmed in the adjustable frequency drive. The Timed Action number is selected from the list when entering parameter
group 23-0* from the LCP. Par. 23-00
then refer to the selected Timed Action number. Each timed action is divided
into an ON time and an OFF time, in which two different actions may be performed.
The actions programmed in timed actions are merged with corresponding actions from digital inputs, control work via bus and Smart Logic ControllerLogic
Controller, according to merge rules set up in 8-5*O-5#, digital/bus.
NOTE!
The clock (parameter group 0-7*) must be correctly programmed for timed actions to function correctly.
NOTE!
When mounting an Analog I/O MCB 109 option card, a battery backup of the date and time is included.
NOTE!
The PC-based configuration tool MCT 10DCT 10 includes a special guide for easy programming of timed actions.
23-00 ON Time
Array [10]
Range:
Function:
Application
dependent*
[Application dependant]
Sets the ON time for the timed action.
NOTE!
The adjustable frequency drive has no backup of the clock function and the set
date/time will reset to default (2000-01-01 00:00) after a power-down unless a
real time clock module with backup is installed. In par. 0-79
Clock Fault
, it is
possible to program for a warning in case the clock has not been set properly,
e.g., after a power-down.
VLT AQUA Low Harmonic Drive Instruction
Manual
6 How to Program the Low Harmonic Drive
MG.20.T1.22 - VLT
®
is a registered Danfoss trademark
6-43