2.1.8 IT Line Power
IT line power
Do not connect adjustable frequency drives with RFI filters to line power supplies with a voltage between phase and ground of more
than 440 V for 400 Vs and 760 V for 690 V drives.
For 400 V IT line power and delta ground (grounded leg), AC line voltage may exceed 440 V between phase and ground.
Par. 14-50
RFI filter
can be used to disconnect the internal RFI capacitors from the RFI filter to ground. Par. 14-50
RFI filter
on both the drive and the
filter must be turned off.
2.1.9 Disposal Instructions
Equipment containing electrical components may not be disposed of together with domestic waste.
It must be separately collected with electrical and electronic waste according to local and currently valid leg-
islation.