Terminal description
There are 4 terminal blocks, 2 with 10 poles and 2 with 8 poles. (See figure below)
MK3A Digital Inputs
MK3B Master / Virtual Master
I1 I2 I3 I4 I5 I6 I7 I8 24V
COM
5V
COM A1
A1
B1
B1
Z1
Z1
MK3C Digital Outputs
MK3D Feedback
O1 O2 O3 O4 O5 O6 O7 O8 24V
COM
5V
COM A2
A2
B2
B2
Z2
Z2
Supply voltages
The option card is supplied by the internal 24 V DC supply of VLT 5000, but as the available power is
limited it can be necessary to use an external 24 V DC supply.
The 24 V DC supply of VLT 5000 can supply a total of 420 mA including the load on the control card
(terminal 12, 13 and output 42 and 45).
The 5 V output on the option card is generated from the 24 V supply. The maximum power on the 5 V
side is 5 V * 280 mA = 1.4 W, this corresponds to app. 60 mA on the 24 V side.
When an external 24 V DC voltage source is used the internal 24 V supply from the control card must
be disconnected, this is done by opening switch 1.1 and 1.2
Each digital input on the option card takes 8 mA. Each digital output on the option card can supply up
to 0.7 A (external 24V-supply) depending on the load. The load from the 24 V supply (internal or
external) can be calculated as follows:
8 mA * number of digital inputs
+
Load on digital outputs
(mk3 C, O1 – O8)
+
load on 5 V supply
(mk3 B/D, 5 V/com)
+
Load on control card
(24 V supply, terminal 12/13 and
outputs, terminal 42/45)