Synchronizing controller
MG.10.N4.02 - VLT is a registered Danfoss trademark
71
O.ERR_13
VLT NOT READY
Cause
VLT is not ready but the PID controller is active.
The VLT status word (Bit 09 and bit 11) is
monitored every 20msec when the PID controller
is active. The VLT is in the “Not ready” state
when:
•
it has an alarm,
•
it is in local mode (parameter 002 = local),
•
local LCP stop is activated,
O.ERR 13 can be reset by toggling input 27.
Note
When pressing local stop on the LCP error 13
may show on the display. To avoid this you can
set parameter 014 to “disable” but that will disable
the stop function of the local control panel.
O.ERR_16
Parameters in EEPROM are corrupted
Meaning
The parameter set recorded in the memory is no
longer correctly available.
Causes
Defective EEPROM or power failure during the
parameter save procedure.
Note
You must re-initialise the parameters by following
the initialising procedure on page 36. If this does
not cure the problem the option card must be
replaced.
O.ERR_17
Programs in EEPROM are corrupted
Meaning
The program data recorded in the memory are no
longer available or no longer correct.
Causes
Defective EEPROM
Note
Replace the option card.
O.ERR_18
Reset by CPU
Meaning
The processor was stopped. This, in turn, was
detected by an internal monitoring circuit (Watch dog)
and automatically triggered a reset.
Causes
Temporary voltage drop, voltage peak or short-circuit.
O.ERR_92
Encoder error
Meaning
There is a short or open circuit on one of the encoder
inputs.
Causes
A defective encoder or a problem with the encoder
cable.
O.ERR xx
Internal error ##
Meaning
If an error like this appears, please perform a power
cycle, if the problem persists the option card must be
replaced.