
Synchronizing controller
MG.10.N4.02 - VLT is a registered Danfoss trademark
23
715
Direction of rotation:
1
= standard, position is counting positive when the drive is running forward.
-1 = position is counting negative when the drive is running forward.
2
= as “1”, but with opposite sign of the reference to the drive. This can be used as
alternative to swapping two motor phases if direction of motor rotation is wrong.
-2
=
as “-1”, but with opposite sign of the reference to the drive. This can be
used as alternative to swapping two motor phases if direction of motor rotation is wrong.
716
Maximum speed: Enter here the maximum speed of the slave drive, measured at the
slave encoder in revolutions per minute.
717
Minimum ramp: Enter here the minimum possible ramp in which the slave drive can
accelerate from 0 to the speed specified in Parameter 716. This is input in milliseconds.
718
Ramp type: Specify here the ramp type to be used.
0 =
linear
ramp
1 =
sinusoidal
ramp
Please note that a sinusoidal ramp requires a greater acceleration torque than a linear
ramp. On the other hand, a sinusoidal ramp produces less stress to the mechanics.
719
Maximum track error: Enter here the maximum track error. This is the permitted error
between the calculated position and the feedback position. If the value is exceeded, the
drive stops and displays the error message: O.ERR_8 “Position error“. The value should
be set higher than the permitted tolerance range ACCURACY in Parameter 733. Input in
quad counts.
720
Reversing behaviour:
0
= means that the slave drive may always reverse, e.g. after overshooting the
target position.
1
= the slave drive may only reverse when the master is reversing.
2
= the slave drive may never reverse.
721
Slave marker type: Select here the type of marker signal for the slave drive:
0
= rising edge of the zero track
1
= falling edge of the zero track
2
= rising edge at I6
3
= falling edge at I6
NOTE:
This parameter is only used in marker synchronizing mode (parameter 725 = 2 or 5).
722
Marker interval at the slave: Enter here the interval between two markers at the slave
drive in quad counts. If this value is not known, it can be determined during the test run.
For procedure, see description in the section “Testing the incremental encoders“ in the
packaging application example.
NOTE:
This parameter is only used in marker synchronizing mode (parameter 725 = 2 or 5).