Synchronizing controller
MG.10.N4.02 - VLT is a registered Danfoss trademark
47
How to program synchronization
Change the value of parameter 701 to “2”. This will start the synchronization program of VLT
5000/VLT 5000 Flux.
To do the synchronization programming you use the following parameters:
Parameter 725
Type of operation: Record “0” or “3” for speed synchronization.
Parameter 726 Hold function: Specify how the drive is to react when Input 29 is activated .
“Hold” switches the drive from master synchronization to a fixed frequency.
Choose “0” to use the frequency set in par. 727 and “1” to use the current
frequency.
Parameter 727 Hold speed: Set here, as a percentage of the maximum speed, the speed at
which the drive should move when you activate Hold and the value “0“ was
selected in Parameter 726.
Parameter 728 Delta hold speed: Set here the step width by which the hold speed is to be
changed upwards or downwards by activating Terminals 32 + 33.
Parameter 737 Gear ratio No.: Record the number of the gear ratio that is to be displayed in
Parameters 738 to 739. Then you set the values required in Parameters 738 to
740. Follow the same procedure for the next gear ratio(s).
Parameter 738 Gear ratio numerator: Record the numerator value of the gear ratio. That is the
encoder pulses of the slave drive. To make fine adjustment possible by means
of inputs 32 and 33 a ratio of for example 7:16 must be programmed as
7000:16000.
Parameter 739 Gear ratio denominator: Enter here the denominator value of the gear ratio.
This value corresponds to the master pulses.
Parameter 743 Step time: In Hold mode, the next frequency change and, in synchronization
mode, the next change of the counter factor of the gear ratio, is carried out
after this time, on the presence of one of the signals at terminal 32 or 33. The
time input is in milliseconds.
Parameter 744 Step width: In speed synchronization, the gear ratio numerator is changed by
this amount, if one of the terminals 32 or 33 is closed.
Parameter 745
Slave speed factor: Record the factor by which the slave speed must be
multiplied, so that it can be displayed. Use the following formula:
Factor =
value
Display
resolution
er
Slaveencod
N
Set
_
*
60
_
*
400
*
Example:
Resolution 1024 increments, desired display 100 at 1500
1
/
min
Factor =
=
100
*
60
1024
*
400
*
1500
.
Re
.
min
1
v
Incr
102400