Synchronizing controller
MG.10.N4.02 - VLT is a registered Danfoss trademark
35
The following are display parameters only (read only)
778
Status of Synchronization
The following status flags are defined for position and marker synchronization. The flags
are not updated when using speed synchronization:
Flag: Decimal value Bit
SYNCREADY
1
0
SYNCFAULT
2
1
SYNCACCURACY
4
2
Only marker Synchronization:
Master marker HIT
8
3
Slave marker HIT
16
4
Master marker Error
32
5
Slave marker Error
64
6
The flags are reset when restarting synchronization (SyncStart).
SYNCACCURACY
Each millisecond it is checked if the actual position deviance between master and slave is
smaller than parameter 733(accuracy), if this is true the SYNCACCURACY flag is set (1),
otherwise the flag is reset. (0).
SYNCFAULT / SYNCREADY
For every marker pulse it is checked whether the SYNCACCURACY flag is present or not.
If it is not present the fault counter is increased and the ready counter set to 0, if it is
present the ready counter is increased and the fault counter set to 0.
If the ready counter is higher than the value set in parameter 735 (marker quantity ready)
then the flag SYNCREADY is set, if not the flag is reset.
If the fault counter is higher than the value in parameter 734 (marker quantity fault) the
flag SYNCFAULT is set (1), if not the flag is reset (0).
Marker HIT flags:
The marker HIT flags are set (1) after detecting n marker pulses (n = parameter 740 and
741).
Marker error flags:
It is checked at each n marker pulse (n = parameter 740 or 741) whether the distance
between the actual marker position and the last registered marker position is lower than
1.8 times the value of parameter 722 or 724. If this is not true, then the associated flag is
set. (1). When using marker windows (par. 751 and 752) it is checked whether a marker
is detected within the window. If no marker is detected the error flag is set (1).
779
Software version number:
The software version of the synchronizing controller in use appears here.
795
“Slave position”: The slave position is displayed in quad counts.
796
“Master position”: The master position is displayed in quad counts.