Synchronizing controller
12
MG.10.N4.02 - VLT is a registered Danfoss trademark
Technical Data
Terminals:
Type..............................................................................................................Plugs with screw connections
Maximum cable size ......................................................................................................1.3 mm
2
(AWG 16)
Digital inputs, MK3A:
Terminal designations .......................................................................................................................I1 – I8
Voltage level ............................................................................................0 – 24 V DC (PNP positive logic)
Voltage threshold logical “0” ............................................................................................................ 5 V DC
Voltage threshold logical “1” .......................................................................................................... 10 V DC
Maximum voltage .......................................................................................................................... 28 V DC
Input impedance .................................................................................................................................. 4 k
Ω
Min. pulse duration (ON INT)........................................................................................................... 1 msec
Galvanic isolation: All digital inputs are galvanically isolated by means of optocouplers,
but with the same common as the digital outputs.
Digital outputs, MK3C:
Terminal designations ................................................................................................................... O1 – O8
Voltage level ............................................................................................................................ 0 – 24 V DC
Maximum load ........................................................................................0.7A (with external power supply)
Update rate ...................................................................................................................................... 1 msec
Galvanic isolation: All digital outputs are galvanically isolated by means of optocouplers,
but with the same common as the digital inputs.
External 24 V DC supply:
(see VLT 5000 manual)
Encoder input 1, MK3B (master):
Terminal designations .......................................................................................... A1,
A1
, B1,
B1
, Z1,
Z1
.
Incremental:
Signal level ...........................................................................................................................5 V differential
Signal type ..................................................................................................................... Linedriver, RS 422
Input impedance .............................................................................................120
Ω
(Dip switch 1.3 = ON)
...................................................................................................................> 24 k
Ω
(Dip switch 1.3 = OFF)
Maximum frequency ...................................................................................... 220 kHz (at 50 % duty cycle)
Phase displacement between A and B..........................................................................................90° ±30°
Absolute:
Signal level ...........................................................................................................................5 V differential
Signal type ............................................................................................................................................. SSI
Data coding ................................................................................................................................ Gray code
Data length ......................................................................................................................................... 25 bit
Parity....................................................................................................................................................none
Clock frequency.................................................................................................................. 105 or 260 kHz
Protocol ............................................................................................................................................... Gray
Maximum positions per revolution .......................................................................................................8192
Maximum number of revolutions .........................................................................................................4096