VLT
®
4000 VT
■
Fuses
UL compliance
To comply with UL/cUL approvals, pre-fuses according to the table below must be used.
200-240 V
VLT
Bussmann
SIBA
Littel fuse
Ferraz-Shawmut
4006
KTN-R30
5017906-032
KLN-R30
ATM-R30 or A2K-30R
4008
KTN-R50
5012406-050
KLN-R50
A2K-50R
4011, 4016
KTN-R60
5014006-063
KLN-R60
A2K-60R
4022
KTN-R80
5014006-080
KLN-R80
A2K-80R
4027, 4032
KTN-R125
2028220-125
KLN-R125
A2K-125R
4042
FWX-150
2028220-150
L25S-150
A25X-150
4052
FWX-200
2028220-200
L25S-200
A25X-200
4062
FWX-250
2028220-250
L25S-250
A25X-250
380-460 V
Bussmann
SIBA
Littel fuse
Ferraz-Shawmut
4006
KTS-R20
5017906-020
KLS-R20
ATM-R20 or A6K-20R
4008
KTS-R25
5017906-025
KLS-R25
ATM-R25 or A6K-25R
4011
KTS-R30
5012406-032
KLS-R30
ATM-R30 or A6K-30R
4016, 4022
KTS-R40
5014006-040
KLS-R40
A6K-40R
4027
KTS-R50
5014006-050
KLS-R50
A6K-50R
4032
KTS-R60
5014006-063
KLS-R60
A6K-60R
4042
KTS-R80
2028220-100
KLS-R80
A6K-80R
4052
KTS-R100
2028220-125
KLS-R100
A6K-100R
4062
KTS-R125
2028220-125
KLS-R125
A6K-125R
4072
KTS-R150
2028220-160
KLS-R150
A6K-150R
4102
FWH-220
2028220-200
L50S-225
A50-P225
4122
FWH-250
2028220-250
L50S-250
A50-P250
4152*
FWH-300/170M3017
2028220-315
L50S-300
A50-P300
4202*
FWH-350/170M3018
2028220-315
L50S-350
A50-P350
4252*
FWH-400/170M4012
206xx32-400
L50S-400
A50-P400
4302*
FWH-500/170M4014
206xx32-500
L50S-500
A50-P500
4352*
FWH-600/170M4016
206xx32-600
L50S-600
A50-P600
4452
170M4017
4502
170M6013
4602
170M6013
4652
170M6013
* Circuit Breakers manufactured by General Electric, Cat .No. SKHA36AT0800, with the rating plugs listed
below can be used to meet UL requirement.
4152
rating plug No.
SRPK800 A 300
4202
rating plug No.
SRPK800 A 400
4252
rating plug No.
SRPK800 A 400
4302
rating plug No.
SRPK800 A 500
4352
rating plug No.
SRPK800 A 600
MG.40.A7.22 - VLT is a registered Danfoss trademark
28