VLT
®
4000 VT
Programming
4 HP (3.00 KW)
[300]
5 HP (4.00 KW)
[400]
7.5 HP (5.50 KW)
[550]
10 HP (7.50 KW)
[750]
15 HP (11.00 KW)
[1100]
20 HP (15.00 KW)
[1500]
25 HP (18.50 KW)
[1850]
30 HP (22.00 KW)
[2200]
40 HP (30.00 KW)
[3000]
50 HP (37.00 KW)
[3700]
60 HP (45.00 KW)
[4500]
75 HP (55.00 KW)
[5500]
100 HP (75.00 KW)
[7500]
125 HP (90.00 KW)
[9000]
150 HP (110.00 KW)
[11000]
200 HP (132.00 KW)
[13200]
250 HP (160.00 KW)
[16000]
300 HP (200.00 KW)
[20000]
350 HP (250.00 KW)
[25000]
400 HP (300.00 KW)
[30000]
450 HP (315.00 KW)
[31500]
500 HP (355.00 KW)
[35500]
600 HP (400.00 KW)
[40000]
✭
Depends on the unit
Function:
This is where to select the kW value P
M,N
that
corresponds to the rated power of the motor.
At the works, a rated kW value P
M,N
has been
selected that depends on the type of unit.
Description of choice:
Select a value that equals the nameplate data on the
motor. There are 4 possible undersizes or 1 oversize
in comparison with the factory setting.
Also, alternatively it is possible to set the value of the
motor power infinitely variable value, see the procedure
for
infinetely variable change of numeric data value
.
103 Motor voltage, U
M,N
(MOTOR VOLTAGE)
Value:
200 V
[200]
208 V
[208]
220 V
[220]
230 V
[230]
240 V
[240]
380 V
[380]
400 V
[400]
415 V
[415]
440 V
[440]
460 V
[460]
480 V
[480]
500 V
[500]
550 V
[550*]
575 V
[575*]
✭
Depends on the unit
* (Must be manually programmed.)
Function:
This is where the rated motor voltage U
M,N
is
set for either star Y or delta
.
Description of choice:
Select a value that equals the nameplate data on
the motor, regardless of the line voltage of the VLT
AFD. Furthermore, alternatively it is possible to set
the value of the motor voltage infinitely variably.
Also refer to the procedure for
infinitely variable
change of numeric data value
.
104 Motor frequency, f
M,N
(MOTOR FREQUENCY)
Value:
50 Hz (50 HZ)
[50]
✭
60 Hz (60 HZ)
[60]
Function:
Select the rated motor frequency f
M,N
.
Description of choice:
Select a value that equals the nameplate
data on the motor.
It is also possible to set the value for motor frequency
infinitely variable in the 24-1000 Hz range.
105 Motor current, I
M,N
(MOTOR CURRENT)
Value:
0.01 - I
VLT,MAX
A
✭
Depends on the choice of motor.
Function:
The rated motor current I
M,N
forms part of the AFD
calculations of torque and motor thermal protection.
MG.40.A7.22 - VLT is a registered Danfoss trademark
69