VLT
®
4000 VT
■
Line supply 3 x 200 - 240 V
According to international requirements
VLT type
4006
4008
4011
Output current
I
VLT,N
[A]
16.7
24.2
30.8
I
VLT, MAX
(60 s) [A]
18.4
26.6
33.9
Output (240 V)
S
VLT,N
[kVA]
6.9
10.1
12.8
Typical shaft output
P
VLT,N
[kW]
4.0
5.5
7.5
Typical shaft output
P
VLT,N
[HP]
5
7.5
10
Max. cable cross-section to motor,brake and DC-bus
[mm
2
]/[AWG]
2
)
4/10
16/6
16/6
Max. input current
(200 V)(RMS) I
L,N
[A]
16.0
23.0
30.0
Max. cable cross-section
power [mm
2
]/[AWG]
2
)
4/10
16/6
16/6
Max. line-fuses
[A]/UL
1)
[A]
50
50
50
Efficiency
3)
0.96
Weight NEMA 1
[lbs]
51
51
51
Weight NEMA 12
[lbs]
77
77
84
Power loss at max. load. [W]
Total
194
194
545
Enclosure
VLT type
NEMA 1/NEMA 12
According to international requirements
VLT type
4016
4022
4027
4032
4042
4052
4062
Output current
I
VLT,N
[A] (200-230 V)
46.2
59.4
74.8
88.0
115
143
170
I
VLT, MAX
(60 s) [A]
(200-230 V)
50.6
65.3
82.3
96.8
127
158
187
I
VLT,N
[A] (240 V)
46.0
59.4
74.8
88.0
104
130
154
I
VLT, MAX
(60 s) [A] (240 V)
50.6
65.3
82.3
96.8
115
143
170
Output
S
VLT,N
[kVA] (240 V)
19.1
24.7
31.1
36.6
41.0
52.0
61.0
Typical shaft output
P
VLT,N
[kW]
11
15
18.5
22
30
37
45
Typical shaft output
P
VLT,N
[HP]
15
20
25
30
40
50
60
Max. cable cross-section to motor and
DC-bus [mm
2
]/[AWG]
2
)
copper
16/6
35/2
35/2
50/0
70/1/0
95/3/0
120/4/0
aluminium
16/6
35/2
35/2
50/0
95/3/0
4)
90/250mcm
4)
120/300mcm
4)
Min. cable, cross-section,
power [mm
2
]/[AWG]
2
)
10/8
10/8
10/8
16/6
10/8
10/8
10/8
Max. input current
(200 V) (RMS) I
L,N
[A]
46.0
59.2
74.8
88.0
101.3
126.6
149.9
Max. cable, cross-section power
[mm
2
]/[AWG]
2
)
copper
16/6
35/2
35/2
50/0
70/1/0
95/3/0
120/4/0
aluminium
16/6
35/2
35/2
50/0
95/3/0
4)
90/250mcm
4)
120/300mcm
4)
Max. line-fuses
[A]/UL
1)
[A]
60
80
125
125
150
200
250
Efficiency
3)
0.95
Weight Chassis
[lbs]
-
-
-
-
180
180
180
Weight NEMA 1
[lbs]
46
60
60
96
202
202
202
Weight NEMA 12
[lbs]
76
98
100
110
208
208
208
Power loss at max. load.:
W
545
783
1042
1243
1089
1361
1613
Enclosure
NEMA 1, NEMA 12
1. See section
Fuses
2. American Wire Gauge
3. Measured using 100 ft. shielded motor cable at rated load and rated frequency.
4. Connection stud 1 x M8 / 2 x M8.
MG.40.A7.22 - VLT is a registered Danfoss trademark
18