Installation
For the units mentioned below, the limits are as follows:
- VLT 4152, 380-460 V, cuts out at 75 °C and can be reset if the temperature is below 60 °C.
- VLT 4202, 380-460 V, cuts out at 80 °C and can be reset if the temperature has fallen below 60° C.
- VLT 4252, 380-460 V, cuts out at 95 °C and can be reset if the temperature has fallen below 65° C.
- VLT 4302, 380-460 V, cuts out at 95 °C and can be reset if the temperature has fallen below 65° C.
- VLT 4352, 380-460 V, cuts out at 105 °C and can be reset if the temperature has fallen below 75° C.
- VLT 4452-4652, 380-460 V, cuts out at 85° C and can be reset if the temperature has fallen below 60°.
- VLT 4102-4152, 525-600 V, cuts out at 75° C and can be reset if the temperature has fallen below
60° C.
- VLT 4202, 525-600 V, cuts out at 80° C and can be reset if the temperature has fallen below 60° C.
- VLT 4252-4402, 525-600 V, cuts out at 100° C and can be reset if the temperature has fallen below
70° C.
•
The VLT AFD is protected against short-circuiting on motor terminals U, V, W.
•
The VLT AFD is protected against ground fault on motor terminals U, V, W.
•
Monitoring of the intermediate circuit voltage ensures that the VLT AFD cuts out if the intermediate circuit
voltage gets too high or too low.
•
If a motor phase is missing, the VLT AFD cuts out.
•
If there is a line fault, the VLT AFD is able to carry out a controlled deramping.
•
If a line phase is missing, the VLT AFD will cut out when a load is placed on the motor.