NOTE
An active HAND-OFF-AUTO signal via the digital
inputs will have higher priority than the control
keys [HAND START]-[AUTO START].
[RESET] is used for resetting the AFD
after an alarm (trip). Can be selected as
Enable
[1] or
Disable
[0] via parameter
015
Reset on LCP
.
See also
List of warnings and alarms.
■
Display mode
In normal operation, any 4 different operating variables
can be indicated continuously: 1.1 and 1.2 and
1.3 and 2. The present operating status or alarms
and warnings that have arisen are shown in line 2
in the form of a number. In the case of alarms, the
alarm in question will be shown in lines 3 and 4,
accompanied by an explanatory note. Warnings will
flash in line 2, with an explanatory note in line 1. In
addition, the display shows the active Setup.
The arrow indicates the direction of rotation; here the
VLT AFD has an active reversing signal. The arrow
body disappears if a stop command is given or if the
output frequency falls below 0.01 Hz. The bottom line
gives the status of the VLT AFD. See next page.
The scroll list on the next page gives the operating
data that can be shown for variable 2 in display mode.
Changes are made via the [+/-] keys.
175ZA694.10
VAR 2
SETUP
1
VAR 1.1 VAR 1.2 VAR
STATUS
■
Display mode, cont.
The table below gives the operating data options
for the first and second line of the display.
Scroll-list:
Unit:
Resulting reference, %
[%]
Resulting reference, unit
[unit]
Frequency
[Hz]
% of maximum output frequency
[%]
Motor current
[A]
Power
[kW]
Power
[HP]
Output energy
[kWh]
Hours run
[hours]
Used-defined readout
[unit]
Setpoint 1
[unit]
Setpoint 2
[unit]
Feedback 1
[unit]
Feedback 2
[unit]
Feedback
[unit]
Motor voltage
[V]
DC-link voltage
[V]
Thermal load on motor
[%]
Thermal load on VLT
[%]
Input status, dig. input
[binary code]
Input status, analog terminal 53
[V]
Input status, analog terminal 54
[V]
Input status, analog terminal 60
[mA]
Pulse reference
[Hz]
External reference
[%]
Heat sink temperature
[°C]
User-defined text
[-]
Three operating data values can be shown in the first
display line, while one operating variable can be shown
in the second display line. To be programmed via
parameters 007, 008, 009 and 010 Display readout.
Status line:
175ZA693.10
40.0Hz
80.0% 5.08A 2.15kW
SETUP
1
AUTO REMOTE RUNNING
HAND LOCAL STOP
RAMPING
JOGGING
.
.
.
.
HAHA
The left part of the status line indicates the control
element of the VLT AFD that is active. AUTO means
that control is via the control terminals, while HAND
indicates that control is via the local keys on the
control unit. OFF means that the VLT AFD ignores
all control commands and stops the motor.