VLT
®
4000 VT
[10]
Setpoint 1 [unit] (SETPOINT 1 [UNITS])
[11]
Setpoint 2 [unit] (SETPOINT 2 [UNITS])
[12]
Feedback 1 (FEEDBACK 1 [UNITS])
[13]
Feedback 2 (FEEDBACK 2 [UNITS])
[14]
Feedback [unit] (FEEDBACK [UNITS])
[15]
Motor voltage [V] (MOTOR VOLTAGE [V])
[16]
DC link voltage [V] (DC VOLTAGE [V])
[17]
Thermal load, motor [%]
(THERM.MOTOR LOAD [%])
[18]
Thermal load, VLT [%]
(THERM.DRIVE LOAD [%])
[19]
Digital input [Binary code] (DIGITAL INPUT [BIN])
[20]
Analog input 53 [V] (ANALOG INPUT 53 [V])
[21]
Analog input 54 [V] (ANALOG INPUT 54 [V])
[22]
Analog input 60 [mA]
(ANALOG INPUT 53 [MA])
[23]
Pulse reference [Hz] (PULSE REFERENCE [HZ])
[24]
External reference [%] (EXT. REFERENCE [%])
[25]
Heat sink temp. [°C] (HEATSINK TEMP [°C])
[26]
LCP Display text (FREE PROG.ARRAY)
[27]
Function:
This parameter allows a choice of the data value
to be shown in the display, line 2, when the VLT
AFD is turned on. The data values will also be
included in the display mode scroll-list.
Parameters 008-010
Small display readout
allow a
choice of another three data values, shown in line
1. See the description of the control unit.
Description of choice:
No readout
can only be selected in parameters
008- 010 Small display readout.
Resulting reference [%]
gives a percentage for
the resulting reference in the range from
Minimum
reference, Ref
MIN
to
Maximum reference, Ref
MAX
. See also reference handling.
Reference [unit]
gives the resulting reference in Hz
in
Open loop
. In
Closed loop
, the reference unit is
selected in parameter 415
Process units
.
Frequency [Hz]
gives the output frequency
from the VLT AFD.
% of maximum output frequency [%]
is the present
output frequency as a percentage value of parameter
202
Output frequency high limit, f
MAX
.
Motor current [A]
states the phase current of the
motor measured as effective value.
Power [HP]
states the actual power consumed
by the motor in HP.
Power [HP]
states the actual power consumed
by the motor in HP.
Output energy [kWh]
states the energy consumed
by the motor since the latest reset was made in
parameter 618
Reset of kWh counter
.
Hours run [Hours]
states the number of hours
that the motor has run since the latest reset in
parameter 619
Reset of hours-run counter
.
User-defined readout [-]
is a user-defined value,
calculated on the basis of the present output frequency
and unit, as well as the scaling in parameter 005
Max. value of user-defined readout
. Select unit in
parameter 006
Unit for user-defined readout
.
Setpoint 1 [unit]
is the programmed setpoint
value in parameter 418 Setpoint 1. The unit
is decided in parameter 415
Process units
.
See also
Feedback handling
.
Setpoint 2 [unit]
is the programmed setpoint value
in parameter 419
Setpoint 2
. The unit is decided
in parameter 415
Process units
.
Feedback 1 [unit]
gives the signal value of the resulting
feedback 1 (Term. 53). The unit is decided in parameter
415
Process units
. See also
Feedback handling
.
Feedback 2 [unit]
gives the signal value of the
resulting feedback 2 (Term. 53). The unit is decided
in parameter 415
Process units
.
Feedback [unit]
gives the resulting signal value
using the unit/scaling selected in parameter 413
Minimum feedback, FB
MIN
, 414
Maximum feedback,
FB
MAX
and 415
Process units
.
Motor voltage [V]
states the voltage supplied
to the motor.
DC link voltage
states the intermediate circuit
voltage in the VLT AFD.
Thermal load, motor [%]
states the calculated/
estimated thermal load on the motor. 100% is the
cut-out limit. See also parameter 117
Motor
thermal protection
.
Thermal load, VLT [%]
states the calculated/
estimated thermal load on the VLT AFD. 100%
is the cut-out limit.
Digital input [Binary code]
states the signal status
from the 8 digital inputs (16, 17, 18, 19, 27, 29, 32
and 33). Terminal 16 corresponds to the bit at the far
left. ‘0
’
= no signal, ‘1
’
= connected signal.
Analog input 53 [V]
states the voltage
value on terminal 53.
Analog input 54 [V]
states the voltage
value on terminal 54.