Connection examples
Start/stop
Start/stop using terminal 18 and coasting stop using
terminal 27.
Par. 302
Digital input
=
Start
[7]
Par. 304
Digital input
=
Coasting stop inver-
ted
[2]
For Precise start/stop the following settings are made:
Par. 302
Digital input
=
Precise start/stop
[27]
Par. 304
Digital input
=
Coasting stop inver-
ted
[2]
Pulse start/stop
Pulse start using terminal 18 and pulse stop using ter-
minal 19. In addition, the jog frequency is activated via
terminal 29.
Par. 302
Digital input
=
Pulse start
[8]
Par. 303
Digital input
=
Stop inverted
[6]
Par. 304
Digital input
=
Coasting stop inver-
ted
[2]
Par. 305
Digital input
=
Jog
[13]
Speed up/down
Speed up/down using terminals 29/33.
Par. 302
Digital input
=
Start
[7]
Par. 303
Digital input
=
Freeze reference
[14]
Par. 305
Digital input
=
Speed up
[16]
Par. 307
Digital input
=
Speed down
[17]
Potentiometer reference
Voltage reference via a potentiometer.
Par. 308
Analog input
=
Reference
[1]
Par. 309
Terminal 53, min. scaling
= 0 Volt
Par. 310
Terminal 53, max. scaling
= 10 Volt
Connection of a 2-wire transmitter
Connection of a 2-wire transmitter as feedback to ter-
minal 60.
Par. 314
Analog input
=
Feedback
[2]
Par. 315
Terminal 60, min. scaling
= 4 mA
Par. 316
Terminal 60, max. scaling
= 20 mA
VLT
®
2800 Series
74
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 2800 Series
Страница 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Страница 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Страница 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Страница 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Страница 103: ......