Operation & Display
001
Language
(language)
Value:
English (english)
[0]
German (deutsch)
[1]
French (francais)
[2]
Danish (dansk)
[3]
Spanish (espanol)
[4]
Italian (italiano)
[5]
Function:
This parameter is used to choose the language to be
shown in the display whenever the LCP control unit is
connected.
Description of choice:
There is a choice of the languages shown. The factory
setting may vary.
002
Local/remote operation
(OPERATION SITE)
Value:
Remote operation (REMOTE)
[0]
Local operation (LOCAL)
[1]
Function:
There is a choice of two different modes of operation
of the frequency converter;
Remote operation
[0] or
Local operation
[1]. See also parameter 013
Local con-
trol
if
Local operation
[1] is selected.
Description of choice:
If
Remote operation
[0] is selected, the frequency con-
verter is controlled via:
1.
the control terminals or via serial communi-
cation.
2.
the [START] key. This cannot, however,
override stop commands transmitted via the
digital inputs or via serial communication.
3.
the [STOP/RESET] and [JOG] keys, on the
condition that these are active.
If
Local operation
[1], is selected, the frequency con-
verter is controlled via:
1.
the [START] key. This cannot, however,
override stop commands via the digital inputs
(see parameter 013
Local control
).
2.
the [STOP/RESET] and [JOG] keys, on the
condition that these are active.
3.
the [FWD/REV] key, on the condition that is
has been selected as active in parameter 016
Local reversing
, and that parameter 013
Local
control
is set at
Local control and open loop
[1] or
Local control as parameter 100
[3]. Pa-
rameter 200
Output frequency range
is set
at
Both directions
.
4.
parameter 003
Local reference
where the ref-
erence can be set using the [+] and [-] keys.
5.
an external control command that can be
connected to the digital inputs (see parame-
ter 013
Local control
).
NB!
The [JOG] and [FWD/REV] keys are lo-
cated on the LCP control unit.
003
Local reference
(LOCAL REFERENCE)
Value:
Par. 013
Local control
must be set to [1]
or [2]:
0 - f
MAX
(par. 205)
50 Hz
Par. 013
Local control
must be set to [3] or
[4].
Ref
MIN
- Ref
MAX
(par. 204-205)
0,0
Function:
In this parameter, the local reference can be set man-
ually. The unit of the local reference depends on the
configuration selected in parameter 100
Configura-
tion
.
Description of choice:
In order to protect the local reference, parameter 002
Local/remote operation
must be set to
Local opera-
tion
[1]. Local reference cannot be set via serial com-
munication.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
10
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 2800 Series
Страница 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Страница 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Страница 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Страница 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Страница 103: ......