415
Maximum feedback, FB
MAX
(Max. feedback)
Value:
FB
MIN
- 100,000.000
1500.000
Function:
See description of parameter 414
Minimum feedback,
FB
MIN
.
Description of choice:
Set the value to be shown on the display when the
maximum feedback has been obtained on the selected
feedback input (parameter 308/314
Analogue inputs
).
416
Process units
(REF/FEEDB. UNIT)
Value:
No unit (No unit)
[0]
% (%)
[1]
ppm (ppm)
[2]
rpm (rpm)
[3]
bar (bar)
[4]
Cycles/min (CYCLE/MI)
[5]
Pulses/s (PULSE/S)
[6]
Units/s (UNITS/S)
[7]
Units/min. (UNITS/MI)
[8]
Units/h (Units/h)
[9]
°C (°C)
[10]
Pa (pa)
[11]
l/s (l/s)
[12]
m
3
/s (m3/s)
[13]
l/min. (l/m)
[14]
m
3
/min. (m3/min)
[15]
l/h (l/h)
[16]
m
3
/h (m3/h)
[17]
Kg/s (kg/s)
[18]
Kg/min. (kg/min)
[19]
Kg/hour (kg/h)
[20]
Tons/min. (T/min)
[21]
Tons/hour (T/h)
[22]
Metres (m)
[23]
Nm (nm)
[24]
m/s (m/s)
[25]
m/min. (m/min)
[26]
°F (°F)
[27]
In wg (in wg)
[28]
gal/s (gal/s)
[29]
Ft
3
/s (ft3/s)
[30]
Gal/min. (gal/min)
[31]
Ft
3
/min. (Ft3/min)
[32]
Gal/h (gal/h)
[33]
Ft
3
/h (Ft3/h)
[34]
Lb/s (lb/s)
[35]
Lb/min. (lb/min)
[36]
Lb/hour (lb/h)
[37]
Lb ft (lb ft)
[38]
Ft/s (ft/s)
[39]
Ft/min. (ft/min)
[40]
Psi (Psi)
[41]
Function:
Select among different units to be shown on the dis-
play. The unit is read out if an LCP control unit can be
connected, and if
Reference [unit]
[2] or
Feedback
[unit]
[3] has been selected in one of parameters
009-012
Display read-out
, and in Display mode. The
unit is used in
Closed loop
also as a unit for Minimum/
Maximum reference and Minimum/Maximum feed-
back.
Description of choice:
Select the required unit for the reference/feedback sig-
nal.
NB!
Parameters 417-421 are only used, if in
parameter 100
Configuration
the selection
made is
Speed regulation, closed loop
[1].
417
Speed PID proportional gain
(SPEED PROP GAIN)
Value:
0.000 (OFF) - 1.000
0.010
Function:
Proportional gain indicates how many times the fault
(deviation between the feedback signal and the set-
point) is to be amplified.
Description of choice:
Quick regulation is obtained at high amplification, but
if the amplification is too high, the process may be-
come unstable in the case of overshooting.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
46
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 2800 Series
Страница 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Страница 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Страница 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Страница 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Страница 103: ......