minal 46 and via the relay output. The unit for feedback
in Closed loop is programmed in parameter 416
Proc-
ess units
.
Description of choice:
Set the required value within the feedback range (pa-
rameter 414
Minimum feedback, FB
MIN
and 415
Max-
imum feedback, FB
MAX
).
229
Frequence bypass, bandwidth
(FREQ BYPASS B.W.)
Value:
0 (OFF) - 100 Hz
0 Hz
Function:
Some systems call for some output frequencies to be
avoided because of mechanical resonance problems
in the system. In parameters 230-231
Frequency by-
pass
these output frequencies can be programmed. In
this parameter a bandwidth can be defined on either
side of these frequencies.
Description of choice:
The frequency set in this parameter will be centered
around parameters 230
Frequency bypass 1
and 231
Frequency bypass 2
.
230
Frequency bypass 1 (FREQ. BYPASS 1)
231
Frequency bypass 2 (FREQ. BYPASS 2)
Value:
0 - 1000 Hz
0.0 Hz
Function:
Some SYSTEMs call for some output frequencies to
be avoided because of mechanical resonance prob-
lems in the SYSTEM.
Description of choice:
Enter the frequencies to be avoided. See also param-
eter 229
Frequency bypass, bandwidth
.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
34
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 2800 Series
Страница 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Страница 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Страница 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Страница 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Страница 103: ......