Preset ref., msb
Preset ref. lsb
0
0
Preset ref. 1
0
1
Preset ref. 2
1
0
Preset ref. 3
1
1
Preset ref. 4
Description of choice:
Set the preset reference(s) that is/are to be the op-
tions.
219
Catch up/Slow down reference
(Catch up/Slw dwn)
Value:
0.00 - 100% of the given reference
0.00%
Function:
In this parameter, the percentage value can be set
which will either be added to or deducted from the re-
mote-controlled references.
The remote-controlled reference is the sum of preset
references, analogue references, pulse reference and
any references from serial communication.
Description of choice:
If
Catch up
is active via a digital input, the percentage
value in parameter 219
Catch up/Slow down refer-
ence
will be added to the remote-controlled reference.
If
Slow down
is active via a digital input, the percentage
value in parameter 219
Catch up/Slow down refer-
ence
will be deducted from the remote-controlled ref-
erence.
221
Current limit, I
LIM
(current limit)
Value:
0 - XXX.X % of par. 105
160 %
Function:
In this parameter, the maximum output current I
LIM
is
set. The factory-set value corresponds to the maxi-
mum output current I
MAX
. If the current limit is to be
used as motor protection, set the rated motor current.
If the current limit is set above 100% (the rated output
current of the frequency converter, I
INV.
), the frequency
converter can only handle a load intermittently, i.e. for
short periods at a time. After the load has been higher
than I
INV.
, it must be ensured that for a period the load
is lower than I
INV.
Please note that if the current limit is
set at a lower value than I
INV.
, the acceleration torque
will be reduced to the same extent.
Description of choice:
Set the required maximum output current I
LIM
.
223
Warning: Low current, I
LOW
(warn. current lo)
Value:
0.0 - par. 224
Warning: High current,
I
HIGH
0.0 A
Function:
If the output current falls below the preset limit I
LOW
a
warning is given.
Parameters 223-228
Warning functions
are out of func-
tion during ramp-up after a start command and after a
stop command or during stop.The warning functions
are activated when the output frequency has reached
the resulting reference. The signal outputs can be pro-
grammed to give a warning signal via terminal 46 and
via the relay output.
Description of choice:
The lower signal limit of the output current I
LOW
must
be programmed within the normal working range of the
frequency converter.
224
Warning: High current, I
HIGH
(warn. current hi)
Value:
0 - I
MAX
I
MAX
Function:
If the output current exceeds the preset limit I
HIGH
a
warning is given.
Parameters 223-228
Warning functions
do not work
during ramp-up after a start command and after stop
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
32
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 2800 Series
Страница 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Страница 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Страница 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Страница 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Страница 103: ......