Special motor characteristic
[8]. It is possible to deter-
mine a U/f characteristic on the basis of four definable
voltages and three frequencies. The voltage at 0 Hz is
set in parameter 133
Start voltage
.
Description of choice:
Set the output voltage (U1) that is to match the first
output frequency (F1), parameter 424
F1 frequency
.
424
F1 frequency
(F1 frequency)
Value:
0.0 - par. 426
F2 frequen-
cy
Par. 104
Motor fre-
quency
Function:
See parameter 423
U1 voltage
.
Description of choice:
Set the output frequency (F1) that is to match the first
output voltage (U1), parameter 423
U1 voltage
.
425
U2 voltage
(U2 voltage)
Value:
0.0 - 999.0 V
par. 103
Function:
See parameter 423
U1 voltage
.
Description of choice:
Set the output voltage (U2) that is to match the second
output frequency (F2), parameter 426
F2 frequency.
426
F2 frequency
(F2 frequency)
Value:
Par. 424
F1 frequency
-
par. 428
F3 frequency
Par. 104
Motor fre-
quency
Function:
See parameter 423
U1 voltage
.
Description of choice:
Set the output frequency (F2) that is to match the sec-
ond output voltage (U2), parameter 425
U2 voltage
.
427
U3 voltage
(U3 voltage)
Value:
0.0 - 999.0 V
par. 103
Function:
See parameter 423
U1 voltage
.
Description of choice:
Set the output voltage (U3) that is to match the third
output frequency (F3), parameter 428
F3 frequency
.
428
F3 frequency
(F3 frequency)
Value:
Par. 426
F2 frequency
-
1000 Hz
Par. 104
Motor fre-
quency
Function:
See parameter 423
U1 voltage
.
Description of choice:
Set the output frequency (F3) that is to match the third
output voltage (U3), parameter 427
U3 voltage
.
NB!
Parameters 437-444 are only used if in
parameter 100
Configuration
a selection
has been made of
Process regulation,
closed loop.
[3].
437
Process PID normal/inverse control
(proc no/inv ctrl)
Value:
Normal (normal)
[0]
Inverse (inverse)
[1]
Function:
It is possible to choose whether the process regulator
is to increase/reduce the output frequency if there is a
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
48
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
Содержание VLT 2800 Series
Страница 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Страница 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Страница 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Страница 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Страница 103: ......