6.2.27 1F9Ah NMT_HostName_VSTR _U32
Index, sub-index Meaning
Meaning
1F9A
NMT_HostName_VSTR Mapped to
12-08 Host
Name
Table 6.29 DNS Host Name
6.2.28 1F9E NMT_ResetCmd_U8
This object is used to reset the frequency converter,
communication or configuration.
Hex value
NMT service
FFh
NMTInvalidService
2Bh
NMTSwReset
28h
NMTResetNode
2Ah
NMTResetConfiguration
29h
NMTResetCommunication
Table 6.30 Reset Command
6.3 2000-5FFF Danfoss Specific Object Area
6.3.1 2000h–5FFFh Vendor Specific Object
Area
The area 2000h to 5FFFh holds the indexes for accessing
the Danfoss frequency converter parameters. All
parameters in the frequency converter are linked to
indexes in this area. The first index available is index
2001h. This index is linked to the frequency converters
0-01 Language
. The rest of the POWERLINK index follows
the same rule, where the frequency converters parameter
number plus 2000h gives the POWERLINK index. For
example, reading the running hours in
15-01 Running
Hours
, is calculated by 2000h + parameter number in hex
number=2000h+5DD=index 25DDh. The XDD file only
contains a subset of the frequency converters parameters.
This subset has the indexes that are required for setting up
the PDO communication. All parameters can be read or
written via SDO communication from the PLC.
Table 6.31
shows a few indexes and their mapping.
Index
Parameter
2001h
0-01 Language
2002h
0-02 Motor Speed Unit
2003h
0-03 Regional Settings
..
2078h
1-20 Motor Power [kW]
2079h
1-22 Motor Voltage
..
24B1h
12-01 IP Address
24B2h
12-02 Subnet Mask
Table 6.31 2000h-5FFFh Vendor Specific Object Area
6.4 6000-Device profile Object Area
6.4.1 6000h–9FFFh Standardised Device
Profile Area
The area 6000h to 9FFFh holds the indexes specified by
the IEC for various device profiles. The Danfoss POWERLINK
does support three profiles, FC Profile, MCO, and the DS
402 profile, velocity mode. The profile is selected via
8-10 Control Word Profile
, Control Word Profile, or via Index
6060h Modes of operation. The profile area has up to 13
indexes depending on the selection made in
8-10 Control
Word Profile
.
Table 6.32
shows the support of indexes, depending on
setting of
8-10 Control Word Profile
(Index 6060h)
Communication Profile Area
MCA 123 POWERLINK Operating Instructions
30
MG92C102 - VLT
®
is a registered Danfoss trademark
6