Bit 12, DSP 402 reserved
Bit 13, DSP 402 reserved
Bit 14, Running/Not running
Bit 14="0" - the motor is not running.
Bit 14="1" - the frequency converter has a valid start signal
or that the output frequency is greater than 0 Hz.
Bit 15, Danfoss reserved
8-10 Control Profile
Option:
Function:
[0]
*
FC profile
[7]
CANopen DSP 402
FC Profile
is the default control profile for the frequency
converter, whereas
CANopen DSP 402
is the CiA
standardized control profile, featuring the special DSP 402
transition state machine.
Illustration 5.6 DSP 402 State Machine
How to Control the Frequenc...
MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT
®
is a registered Danfoss trademark