Cascade Controller Option
Parameter group 700,
all parameters
■
Parameter group 700 definitions
Para
Name
Description
Unit
Range
Factory
Setting
Change
During
Operation
Data Type
Conversion
Index
712
PUMP COMBINA-
TION
Selects number and size of
slave pumps
No.
1 - 8
R6@100
No
5
0
713
STAGING BANDW.
%
Pump Staging Bandwidth in
% of setpoint
%
1.0 - 100.0
5.0%
Yes
6
-1
714
DESTAGING DELAY
Pump Staging Bandwidth off
Sec.
0.0 - 3000.0
10 sec.
Yes
6
-1
715
STAGING DELAY
Pump Staging Bandwidth on
Sec.
0.0 - 3000.0
10 sec.
Yes
6
-1
716
OVERRIDE
BANDW.%
Over-ride Bandwidth
%
2.0 - 100.0
100%
Yes
6
-1
717
OVERRIDE TIMER
Over-ride Bandwidth
hysteresis time
Sec.
0.0 - 300
10 sec.
Yes
6
-1
718
STAGING FREQ%
VLT Frequency at staging
transition in % of max speed
%
0.0 - 100.0
90%
Yes
6
-1
721
DESTAGE TIME
Destage timer
Sec.
Para 403 - 600
OFF
Yes
6
0
722
PUMP CYCLING
Enable or disable pump
cycling
Enabled/Disabled
Enable
No
5
0
723
OPERATIONAL
MODE SELECT
Selects either Standard or
Master/Slave control
Standard/Master
Slave
Standard
No
5
0
724
PUMP 2 ON TIME
Hour meter for pump 2
Hrs
0 - 130000
0.0
Yes
7
-1
725
PUMP 3 ON TIME
Hour meter for pump 3
Hrs
0 - 130000
0.0
Yes
7
-1
726
PUMP 4 ON TIME
Hour meter for pump 4
Hrs
0 - 130000
0.0
Yes
7
-1
727
PUMP 5 ON TIME
Hour meter for pump 5
Hrs
0 - 130000
0.0
Yes
7
-1
728
PUMP 2 CYCLES
Cycle counter for pump 2
No.
0 - 130000
0.0
Yes
7
0
729
PUMP 3 CYCLES
Cycle counter for pump 3
No.
0 - 130000
0.0
Yes
7
0
730
PUMP 4 CYCLES
Cycle counter for pump 4
No.
0 - 130000
0.0
Yes
7
0
731
PUMP 5 CYCLES
Cycle counter for pump 5
No.
0 - 130000
0.0
Yes
7
0
736
RELAY ON TIME
Relay hour meter, relay R6 -
R9
Hrs
0 - 130000
0.0
No
7
-1
737
RELAY CYCLES
Relay Cycle counter, rela
No.
0 - 130000
0.0
No
7
-1
738
SETPOINTS HM 1- 7
Calculated intermediate
setpoint, relay (Hm1-Hm7)
Para
415
H0 - H1
0.000
No
4
-3
739
M/S STAGE FREQ
M/S Stage on frequency, relay
(1-4)
Hz
Para 201-202
Para 202
Yes
6
-1
740
M/S DESTAGE FREQ
M/S Stage off frequency, relay
(1-4)
Hz
Para 201-202
Para 201
Yes
6
-1
Conversion Index Factors
Conversion Index
Conversion Factor
74
3.6
2
100.0
1
10.0
0
1.0
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
DataType Descriptions
Data type
Description
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Text string
MG.60.I3.02 - VLT is a registered Danfoss trademark
57