Cascade Controller Option

User Interface

Three operating data values can be shown in the

first display line and one in the large display line,

programmed via parameters 007, 008, 009, and 010.

Display mode I

´

In Display mode I, the drive is in Auto mode with

reference and control determined via the control

terminals. Below is an example in which the drive

is running in setup 1, in Auto mode, with a remote

reference, and at an output frequency of 40 Hz.

The text in line 1, FREQUENCY, describes the

meter shown in the large display. Line 2 (large

display) shows the current output frequency (40.0

Hz), direction of rotation (reverse arrow), and active

setup (1). Line 3 is blank. Line 4 is the status line

and the information is automatically generated for

display by the drive in response to its operation. It

shows that the drive is in auto mode, with a remote

reference, and that the motor is running.

175ZA683.10

SETUP

1

FREQUENCY

40.0Hz

40.0Hz

40.0Hz

40.0Hz

40.0Hz

AUTO REMOTE RUNNING

Status line (Line 4): Additional automatic displays

for the drive status line are shown below.

175ZA684.10

40.0Hz

80.0% 5.08A 2.15kW

SETUP

1

AUTO REMOTE RUNNING

HAND LOCAL  STOP

OFF         RAMPING
            JOGGING
            .

            .

            .

            .
            STAND BY

The left indicator on the status line displays the

active control mode of the VLT drive. AUTO is

displayed when control is via the control terminals.

HAND indicates that control is local via the keys

on the LCP. OFF indicates that the drive ignores

all control commands and will not run.

The center part of the status line indicates the

reference element that is active. REMOTE means that

reference from the control terminals is active, while

LOCAL indicates that the reference is determined

via the [+] and [-] keys on the control panel.

The last part of line 4 indicates the drive

s operational

status, for example: RUNNING, STOP, or ALARM.

Display mode II

This display mode shows three operating data values

in the top line programmed via parameters 007,

008, and 009. Pressing the [DISPLAY MODE] key

toggles between Display modes I and II.

175ZA685.10

50.0Hz

SETUP

1

AUTO REMOTE RUNNING

100% 7.8A 5.9kW

Display mode III

Press and hold the [DISPLAY MODE] key while in Mode

II. Mode III is visible as long as the key is depressed.

The top line changes to identify the data names and

units displayed. Lines 2 and 4 are unchanged. When

the key is released, the display returns to Mode II.

175ZA686.10

60.0Hz

SETUP

1

AUTO REMOTE RUNNING

REF% CURR.A.POW.,KW

Display mode IV

This display mode is used for local operation, where

the local speed reference is given from the keypad. In

this display mode, the reference is determined via the

[+] and [-] keys. Control is carried out through the

bottom keys on the keypad. The first line indicates

the required reference. The third line gives the relative

value of the output frequency in the form of a bar

graph in relation to the maximum frequency.

175ZA688.10

40.0Hz

HAND LOCAL RUNNING

USE +/-         40Hz

Changing data

Regardless of whether a parameter has been selected

under the Quick Menu or the Extend Menu, the

procedure for changing data is the same. Pressing

the [CHANGE DATA] key gives access to changing

the selected parameter. Line 3 displays the parameter

MG.60.I3.02 - VLT is a registered Danfoss trademark

25

Содержание Cascade

Страница 1: ...21 Introduction 21 Changed systemstop functions 22 Serial communications parameter 500 22 User Interface 23 How to use the LCP for programming 23 Control keys for parameter setup 23 Indicator lamps 23...

Страница 2: ...back Transmitter Wiring 54 Connecting feedback transmitters 54 Single 0 10 V feedback transmitter connection 54 Two 0 10 V feedback transmitter connections 54 Two 4 20 mA feedback transmitters connect...

Страница 3: ...AQUA Operating Instructions When reading through this Operating Instructions you will come across various symbols that require special attention The symbols used are the following Indicates a general...

Страница 4: ...against motor overload is included in the factory setting Parameter 117 Motor thermal protection default value is ETR trip 1 For the North American market The ETR functions ensure overload protection...

Страница 5: ...parts may be fatal even after the equipment has been disconnected from mains 200 240 and 380 480 V wait at least 15 minutes 550 600 V VLT 6002 8002 6027 8027 wait at least 15 minutes 550 600 V VLT 603...

Страница 6: ...n response to actual system demand The VLTs PID controller accommodates two feedback signals and two setpoints which allows regulating a system with different setpoint zones In pumping applications wh...

Страница 7: ...d control when the drive runs continuously at minimum speed with one or more constant speed motors running Since a variable speed pump at minimum speed adds no or very limited flow to the system it is...

Страница 8: ...at the same speed the possibility of running a pump continuously into a closed check valve is all but eliminated This reduces pump maintenance by minimizing the wear on pump seals and bearings Danfos...

Страница 9: ...ed in this chapter to 7 1 in lbs 0 8 Nm unless specified otherwise Optional transmitter connections VLT drive terminals12 and 13 provide a 24 VDC 200 mA power supply This supply can be used to power r...

Страница 10: ...s Drive configurations vary 2 Disconnect VLT Drive Control Wiring Touching electrical parts may be fatal even after equipment has been disconnected from AC line To be sure that capacitors have fully d...

Страница 11: ...es Lift control board cassette from bottom Disconnect two ribbon cables from VLT control board Unhinge cassette at top to remove 4 Remove LCP Keypad Cradle Push tabs at side of LCP cradle to release c...

Страница 12: ...ller option card through slot at side of VLT control board cassette Option card mounts with component side down Feed plastic option card insulation pad through terminal opening in control board casset...

Страница 13: ...ollar A of control board ribbon cable socket DO NOT remove blue insulation on end of option card ribbon cable Insert ribbon cable into corresponding socket B on VLT control board and push collar close...

Страница 14: ...ounding strips in VLT chassis can vary with drive configuration When applicable remove mounting screws located in chassis using Torx T 20 screw driver and save for reassembly Otherwise grounding strip...

Страница 15: ...cables to control board in corresonding connectors as removed in step 3 Hinge VLT cassette at top of VLT chassis and reposition into place Use Torx T 20 screwdriver to fasten two captive screws Ensure...

Страница 16: ...d insert into slot in side of control card cassette Attach insulation pad to top most clamp position with one screw from removed wiring clamp Route VLT control terminal wiring through bottom left wiri...

Страница 17: ...wiring diagram shows an example for a standard cascade control system with 4 fixed speed motors a 4 20 mA pressure transmitter and external safety interlock Power terminal connections Control board t...

Страница 18: ...or The HAND position allows manual operation of the motor The motor can be disabled by setting the switch to OFF For a motor in the OFF position the cascade controller will try to start it by triggeri...

Страница 19: ...emonstrates a 4 20 mA pressure transmitter an external safety interlock and four slave drives The slave drive speed reference is provided from terminal 17 as a pulse signal The relays on the option ca...

Страница 20: ...in the same way receiving the Start Stop command and a pulse speed reference from the master drive The speed reference and its common are typically looped from Slave to Slave Power terminal connectio...

Страница 21: ...e and Cascade Controller Card Setup New options are also available to stop pumps or fans controlled in cascade operation A summary of VLT changed functionality is presented in this chapter Changed Def...

Страница 22: ...a stop STOP via Terminal 27 Coast Inverse parameter 304 Constant speed motors stop immediately Controller coasts its motor to a stop STOP via Terminal 27 Safety Interlock parameter 304 Constant speed...

Страница 23: ...xtend Menu or the Quick Menu mode CANCEL is used if a change to a selected parameter is not to be carried out OK is used for confirming a change to a selected parameter are used to scroll through para...

Страница 24: ...Parameters 008 009 and 010 select the data displayed on the top line Parameter 007 Large Display Readout selects the data displayed on line 2 The list on the next page defines the operating data that...

Страница 25: ...tus line indicates the reference element that is active REMOTE means that reference from the control terminals is active while LOCAL indicates that the reference is determined via the and keys on the...

Страница 26: ...voltage and parameter 104 Motor frequency Parameter setting procedure Enter or change parameter data or settings as follows 1 Press Quick Menu or Extended Menu key 2 Use and keys to find parameter yo...

Страница 27: ...t reset when using manual initialization 500 Protocol 600 Operating hours 601 Hours run 602 kWh counter 603 Number of power ups 604 Number of overtemperatures 605 Number of overvoltages 724 737 Operat...

Страница 28: ...ller efficiency after system start up Items 2 6 are motor characteristics In Standard cascade control mode only the motor data from the variable speed motor run by the cascade controller are entered I...

Страница 29: ...Ref max 0 019 205 Ref max Units Ref min Max feedback 0 020 723 Operational Mode select Standard M S Standard Cascade 021 712 Pump combination 1 8 1 022 713 Staging BandW 1 0 100 0 10 0 023 714 Destag...

Страница 30: ...250 00 400 HP 300 00 KW 300 00 450 HP 315 00 KW 315 00 500 HP 355 00 KW 355 00 600 HP 400 00 KW 400 00 Depends on the unit Function This sets the power value that corresponds to the nameplate power o...

Страница 31: ...will be unable to run continuously below this value in any mode Description of choice Set a value from 0 0 Hz to the Output frequency high limit set in Quick Menu item 008 parameter 202 Quick Menu 00...

Страница 32: ...ut 0 10 V a pull down resistor of 500 should be fitted to terminal 39 common for analogue digital outputs See chapter 10 for additional detail If the output is used as a current output the resulting i...

Страница 33: ...n the Display mode and as a unit for Minimum Maximum Feedback Minimum Maximum Reference Warning Feedback High Low and for the H1 H0 and the calculated Hmx parameter settings readings Description of ch...

Страница 34: ...and via the relay outputs In Closed loop the unit for the feedback is programmed in parameter 415 Units related to closed loop Description of choice Set the desired value within the feedback range be...

Страница 35: ...ystem using variable speed pumps controlled by a Master drive NB Set the correct control option Improper setting may result in system damage operational errors or wasted energy Description of choice S...

Страница 36: ...be selected in parameter 004 to omit downloading motor and current dependent data Extended Menu Par 002 Active Setup ACTIVE SETUP Value Factory Setup FACTORY SETUP 0 Setup 1 SETUP 1 1 Setup 2 SETUP 2...

Страница 37: ...load all parameters to copy all parameter values from the drive to the LCP Select Download all parameters to copy all parameter values from the LCP to the drive on which the keypad is mounted Select D...

Страница 38: ...e the 39 parameters are programmed in sequence Procedures for programming are in the following order Initial Setup Quick Menu items 1 20 Step 1 Standard control mode programming Step 2 Optimization of...

Страница 39: ...n Standard cascade control mode additional pumps can be either 100 200 or 300 relative to the VLT driven pump Description of choice Select the pump combination and capacities from the choices offered...

Страница 40: ...ime DESTAGING DELAY Value 0 3000 sec 30 sec Function Immediate destaging of a fixed speed pump is not desirable when a momentary pressure increase in the system that exceeds the staging bandwidth SBW...

Страница 41: ...be optimized with increased familiarity with the system See parameter 717 Override Bandwidth Timer Commissioning the Cascade Controller To avoid unintended staging during the commissioning phase and f...

Страница 42: ...tion frequency might cause the check valve at the discharge of a variable speed pump to close during the transition which could add pressure in the system Ensure that the transition frequency setting...

Страница 43: ...edback signal originates at the far end of the system the drive does not need to compensate for system pressure changes due to flow For this system configuration or for two setpoint PID control or for...

Страница 44: ...ed off Not operating a pump over long time periods can create corrosion concerns If cycling is disabled the controller follows the fixed pattern of relay activation 6 7 8 and 9 regardless of the runni...

Страница 45: ...Menu is accessed by pressing the EXTEND MENU key on the drive control panel Parameter 418 may be accessed through either the Extended Menu or as item 28 in the Quick Menu EXTENDED MENU Par 417 Feedba...

Страница 46: ...e program available on the Danfoss website By entering pump and system data MUSEC provides the programmer with Master drive on and off staging frequencies for each pump at optimal efficiency For a fre...

Страница 47: ...Function Staging delay time is used to prevent the fast cycling on of the slave pumps or fans Increase the time if frequent switching is encountered Description of choice Set staging on delay time In...

Страница 48: ...its Quick Menu 031 Par 722 Pump cycling PUMP CYCLING Value Enabled Disabled Enabled Function To achieve equal hours of operation use of pumps or fans can be cycled Timers on the relay outputs relays 6...

Страница 49: ...uency for each pump After pressing the CHANGE DATA key in parameter 740 use the and keys to scroll through all four slave settings If the pump or system data is unknown refer to the section Alternativ...

Страница 50: ...uency low limit Alternate Feedback Programming In water supply systems it is often impractical to place a pressure sensor at the far end of the system In HVAC and other applications however it is ofte...

Страница 51: ...t reference for one setpoint PID control or for the setpoint for zone 1 in two setpoint PID control Description of choice Set the required value the system is to maintain during normal operation The v...

Страница 52: ...efore PID control is activated The drive will follow the acceleration ramp when a start signal is received as if in open loop When the programmed start frequency is reached it will change to closed lo...

Страница 53: ...ct and become unstable See Optimization of the Process Regulator for information on proper adjustment Procedure for Optimization of the Process Regulator The process regulator is set by Quick Menu ite...

Страница 54: ...CK Transmitter high limit 308 AI V 53 FUNCT NO OPERATION 311 AI V 54 FUNCT NO OPERATION 314 AI mA 60 FUNCT FEEDBACK 315 AI 60 SCALE LOW 4 mA 316 AI 60 SCALE HIGH 20 mA Single 0 10 V feedback transmitt...

Страница 55: ...T NO OPERATION Two feedback signals and two setpoints Similar to two feedback signals and one setpoint the need for two feedback signals with two setpoints is frequently encountered Whenever two criti...

Страница 56: ...I mA 60 FUNCT NO OPERATION The reference range is generally set to equal the range of the transmitter In this way the setpoint reference can be set to any value that the transmitter can produce If req...

Страница 57: ...ur meter for pump 2 Hrs 0 130000 0 0 Yes 7 1 725 PUMP 3 ON TIME Hour meter for pump 3 Hrs 0 130000 0 0 Yes 7 1 726 PUMP 4 ON TIME Hour meter for pump 4 Hrs 0 130000 0 0 Yes 7 1 727 PUMP 5 ON TIME Hour...

Страница 58: ...o of times each relay pump is switched on The cycle counter can be reset to zero when a pump is replaced Par 736 Relay on time RELAY ON TIME Value h 0 130000 Function The relay timer accumulates the h...

Страница 59: ...ch is located on the VLT control card Digits 3 6 indicate the four relays of the cascade controller relays 06 07 08 and 09 which are located on the option board Digits 7 8 are reserved for future use...

Отзывы: