Cascade Controller Option
Transmitter ratings:
Supply: 15 - 30 VDC
Output: 0 - 10 V
Range: 0 - 100 Pa
The VLT is programmed to match its input to follow
the specification of the transmitter:
Programming:
Parameter
Parameter
Parameter
Number
Description
Value
100
CONFIG. MODE
CLOSED LOOP
415
Ref./FDBK UNIT
Pa
413
MIN. FEEDBACK
0
414
MAX. FEEDBACK
100
308
AI [V] 53 FUNCT.
FEEDBACK
309
AI 53 SCALE LOW
0
310
AI 53 SCALE HIGH
100
311
AI [54] 54 FUNCT.
FEEDBACK
312
AI 54 SCALE LOW
0
313
AI 54 SCALE HIGH
100
314
AI [mA] 60 FUNCT.
NO OPERATION
The reference range is generally set to equal the
range of the transmitter. In this way, the setpoint
(reference) can be set to any value that the transmitter
can produce. If required, the reference range can be
set to a range that is narrower than the transmitters
range, but it cannot be set to a wider range.
Parameter
Parameter
Parameter
Number
Description
Value
204
MIN. REFERENCE
0
205
MAX. REFERENCE
100
In this example, load 1 requires a pressure of at
least 30 Pa and load 2 at least 60 Pa.
Parameter
Parameter
Parameter
Number
Description
Value
417
2 FEEDBACK CALC.
2 ZONE MIN
418
SETPOINT 1
30
419
SETPOINT 2
60