Cascade Controller Option
VLT Drive and Cascade
Controller Setup
■
Quick Menu Summary
Quick Menu
number
Parame-
ter num-
ber
Name
Units
Range
Factory setting
Basic Drive Set Up parameters
001
001
Language
10 languages
See VLT 6000 HVAC or VLT
8000 AQUA manuals.
002
102
Motor Power
KW/HP
1.1-450/1.5-600
003
103
Motor Voltage
Volts
200 - 480
004
104
Motor Frequency
Hz
50 / 60
005
105
Motor Current
Amps
0-IVLT max
006
106
Rated Motor Speed
RPM
0- fm,n x 60
007
201
Min. Frequency
Hz
0.0 -fmax
2/5 of fnom (NEW)
008
202
Max. Frequency
Hz
Fmin-120/1000
Fnom x 1.1 (NEW)
009
206
Ramp up time
Seconds
1-3600
See table above in 2.4.8
010
207
Ramp down time
Seconds
1-3600
011
323
Relay 1 Output
Depending on choice
See VLT 6000 HVAC Manual.
012
326
Relay 2 Output
Basic Set Up for Standard Cascade and Master/Slave.
013
415
Closed loop units
Selected according to your process.
014
413
Minimum Feedback
015
414
Maximum Feedback
016
227
Warning low Feedback
Units
-999,999.999- FB High
-999,999.999
017
228
Warning high Feedback
Units
FB low- 999,999.999
999,999.999
018
204
Ref.min.
Units
Min. feedback - Ref.max
0
019
205
Ref.max.
Units
Ref.min - Max. feedback
0
020
723
Operational Mode select
-
Standard / M/S
Standard Cascade
021
712
Pump combination
1 - 8
1
022
713
Staging BandW.
%
1.0 - 100.0
10.0
023
714
Destaging Delay
Sec.
0.0 - 3000
15
024
715
Staging Delay
Sec.
0.0 - 3000
15
025
716
Override BW
% of set point
2.0 - 100.0
20.0
026
717
Override Timer
Sec.
0.0 - 300
5
027
718
Transition frequency
% of fnom
fmin - 120.0
60
028
418
Setpoint 1 (H0)
Bar (or equiv.)
Refmin - Refmax
6 bar
029
419
Setpoint 2 (H1)
Bar (or equiv.)
Refmin - Refmax
6 bar
030
721
Destage Timer
Timer Sec.
0.0 - 600
30
031
722
Pump cycling
Enabled/Disabled
Enabled
032
319
Analog/digital outputs
-
[1] - [43]
F out 020mA
033
739
M/S Stage on frequencies
Hz
F min - F max
F min
034
740
M/S stage off frequencies
Hz
F min - F max
F max
PID Controller tuning
035
420
Normal/Inverse control
Normal/Inverse
Normal mode
036
422
PID Start up frequency
Hz
Fmin-fmax
0 Hz
037
427
PID Lowpass filter time
Sec.
0.01 10.00
1.00
038
423
PID Proportional Gain
Factor
0.00 10.0
0.01
039
424
PID Integrator time
Sec.
0.01 9999.0
OFF
■
Language
Quick Menu 001 Par. 001 Language
(LANGUAGE)
Value:
✭
English (ENGLISH)
German (DEUTSCH)
French (FRANCAIS)
Danish (DANSK)
Spanish (ESPAÑOL)
Italian (ITALIANO)
Swedish (SVENSKA)
Dutch (NEDERLANDS)
MG.60.I3.02 - VLT is a registered Danfoss trademark