Cascade Controller Option
■
Feedback Transmitter Wiring
■
Connecting feedback transmitters
Terminal 12 and 13 of the VLT provide access to a
24 VDC, 200 mA power supply. This can be used
to power remote transmitters, so an external power
supply is generally not needed. The diagrams below
show how to wire two- and three-wire transmitters.
Single 4 - 20 mA feedback transmitter connection:
Programming:
Parameter
Parameter
Parameter
Number
Description
Value
415
REF./FDBK UNIT
Process unit
413
MIN. FEEDBACK
Transmitter low limit
414
MAX. FEEDBACK
Transmitter high limit
308
AI [V] 53 FUNCT.
NO OPERATION
311
AI [V] 54 FUNCT.
NO OPERATION
314
AI [mA] 60 FUNCT
FEEDBACK
315
AI 60 SCALE LOW
4 mA
316
AI 60 SCALE HIGH
20 mA
Single 0 - 10 V feedback transmitter connection:
Programming:
Parameter
Parameter
Parameter
Number
Description
Value
415
REF./FDBK UNIT
Process unit
413
MIN. FEEDBACK
Transmitter low limit
414
MAX. FEEDBACK
Transmitter high limit
308
AI [V] 53 FUNCT.
FEEDBACK
309
AI 53 SCALE LOW
0 V
310
AI 53 SCALE HIGH
10 V
314
AI [mA] 60 FUNCT
NO FUNCTION
Two 0 - 10 V feedback transmitter connections:
When two feedback signals are used with the
VLT, both signals must be voltage signals. Both
transmitters must also have the same range.
MG.60.I3.02 - VLT is a registered Danfoss trademark