Cascade Controller Option
VLT Drive and Cascade
Controller Setup
Quick Menu 012 Par. 326 Output relay 2
(RELAY 2 FUNCTION)
Value:
29 optional settings
✭
RUNNING
Function:
This output activates relay switch 02. This low voltage
relay is generally programmed to provide a remote
run indication. There are 29 optional settings.
Running
makes this relay close when the drive
is running. This is the default setting.
Description of choice:
Select relay 2 function.
Quick Menu 013 Par. 415 Units relating
to closed loop
(REF. / FDBK. UNIT)
Value:
No unit
[0]
✭
%
[1]
rpm
[2]
ppm
[3]
pulse/s
[4]
l/s
[5]
l/min
[6]
l/h
[7]
kg/s
[8]
kg/min
[9]
kg/h
[10]
m
3
/s
[11]
m
3
/min
[12]
m
3
/h
[13]
m/s
[14]
mbar
[15]
bar
[16]
Pa
[17]
kPa
[18]
mVS
[19]
kW
[20]
C
[21]
GPM
[22]
gal/s
[23]
gal/min
[24]
gal/h
[25]
lb/s
[26]
lb/min
[27]
lb/h
[28]
CFM
[29]
ft
3
/s
[30]
ft
3
/min
[31]
ft
3
/h
[32]
ft/s
[33]
in wg
[34]
ft wg
[35]
PSI
[36]
lb/in
2
[37]
HP
[38]
F
[39]
Function:
This unit will be used for the reading in the Display
mode and as a unit for
Minimum / Maximum
Feedback, Minimum / Maximum Reference, Warning
Feedback High/Low
and for the
H1, H0
and the
calculated
Hmx
parameter settings/readings.
Description of choice:
Select the unit for the reference/feedback signal.
Quick Menu 014 Par. 413 Minimum feedback
(MIN. FEEDBACK)
Value:
-999,999.999 - FB
MAX
✭
0.000
Function:
Parameters 413,
Minimum feedback
and 414,
Maximum feedback
are used to scale the feedback
signal ensuring that it shows the feedback signal
proportionally to the signal at the input.
Description of choice:
Set the value to be shown on the display when the
feedback signal is at its minimum value.
Quick Menu 015 Par. 414 Maximum feedback
(MAX. FEEDBACK)
Value:
FB
MIN
- 999,999.999
✭
100.000
Function:
Parameters 413,
Minimum feedback
and 414,
Maximum feedback
are used to scale the feedback
signal ensuring that it shows the feedback signal
proportionally to the signal at the input.
Description of choice:
Set the value to be shown on the display when the
feedback signal is at its maximum value.
MG.60.I3.02 - VLT is a registered Danfoss trademark
33