34
Fan Always On / FAo
If this parameter is set to yES, all other parameters in this section
about the fan are deactivated .
NOTE:
If FAo is set to nO, then the following parameters will be applied.
Fan On Delay / Fod
Fan Stop Delay / FSd
If this parameter and FSd are both set to zero then the fan runs whenever the
compressor runs .
Fod defines the fan delay
(in seconds) after a compressor
cut-in .
FSd defines the fan delay after a
compressor cut-out .
7.5 Fan /
FAn
ERC menu
code
Default
Min
Max
Unit
Conv
Unit
Scale
Default Access
Shop Ser OEM
Fan
FAn
Fan always On
FAo
yES
no
yES
no
1
-- -- RW
Fan stop time on door open
Fdt
999
0
999
no
Sec
1
-- -- RW
Fan On Delay
Fod
0
0
240
no
Sec
1
-- -- RW
Fan Stop delay
FSd
0
0
240
no
Sec
1
-- -- RW
Fan On Cycle
FoC
0
0
960
no
Sec
1
-- -- RW
Fan Stop Cycle
FSC
0
0
960
no
Sec
1
-- -- RW
The fan parameters are all related to energy saving,
and to redistribution of air within the cabinet to
reduce the amount of energy spent on cooling .
Fan On Cycle / FoC
Fan Stop Cycle / FSC
When the compressor is off, and FoC or FSC are not zero, the fan runs in cycles
according to FoC and FSC .
Example: FoC = 120 [sec] and FSC = 120 [sec] means that the fan runs for half the
time when the compressor is off . When the compressor is on, the fan is always on
(according to FAo and Fod) .
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
ERC
102 Reference manual – 7 PARAMETERS
Fan stop time on door open: Fdt
The maximum time the fan will be stopped after the door has been opened .
0: fan will not stop under opening
1-998: number of seconds fan will be stopped during door opening
999: fan will be stopped as long as the door is open
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint