36
Light Blocking delay / Lbd
If the cooler is placed where the ambient light is unstable, the ambient light sensor
can cause the cooler to toggle between ECO and normal mode .
The light blocking delay disables the light-sensor for a given time after ambient
light change from bright to dark, so that the cooler stays in ECO mode for at least
this time . When the cooler is in serving or pull-down mode, the light sensor is
de-activated and a change to ECO mode will be determined by the door-sensor .
0: No blocking of the ambient light sensor .
Eco Temperature Offset / Eto
This parameter gives a relative temperature in degrees . It is the difference in
temperature for Eco mode operation compared to Normal mode .
NOTE:
Setting a temperature offset may be illegal in
some jurisdictions.
Pull down (sometimes known as Super Cool) is
a procedure for improving cooling performance,
accelerating the time used to reach the desired
temperature . Pull Down settings overrule all
other settings .
7.7 Pull Down /
Pud
Danfoss ERC 102
ERC Front and Button Functionallity:
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
ERC menu
code
Default
Min
Max
Unit
Conv
Unit
Scale
Default Access
Shop Ser OEM
Pull Down
Pud
Pull-down Initiate
Temperature
Pit
50 .0/122 .0 -40 .0/-40 .0 50 .0/122 .0
C/F a
°C/°F
.1
-- -- RW
Pull-down Cycling
PCy
30
0
360
no
min
1
-- -- RW
Pull-down defrost Interval
Pdi
15
0
48
no
hour
1
-- -- RW
Pull-down duration
Pdd
24
0
48
no
hour
1
-- -- RW
Pull-down limit temp
PLt
0 .0/32 .0 -55 .0/-67 .0 55 .0/131 .0
C/F a
°C/°F
.1
-- -- RW
Pull-down reduction
temp △t
Prt
0 .1/0 .2
0,0
10 .0/16 .0
C/F r
K/°R
.1
-- -- RW
ERC
102 Reference manual – 7 PARAMETERS