Operating Limits 

Environment 

This equipment is designed for indoor installation only. 

Sheltered locations such as attics, garages, etc., generally 

will not provide sufficient protection against extremes in 

temperature and/or humidity, and equipment performance, 

reliability, and service may be adversely affected.

Additional Information 

Units are designed to start and operate with entering 

air at 40˚F (4˚C), with entering water at 70˚F (21˚C), 

with both air and water at the flow rates used in the ISO 

Standard 13256-1 rating test, for initial start-up in winter. 

Note: 

This is not a normal or continuous condition. It is 

assumed that such a start-up is for the purpose 

of bringing the building space to occupancy tem

-

perature.

Table 4: Air limits in °F (°C)

Air Limits

Cooling

Heating

Minimum Ambient Air

1

40

°

F (4

°

C)

40

°

F (4

°

C)

Rated Ambient

80

°

F (27

°

C)

70

°

F (21

°

C)

Maximum Ambient Air

2

100

°

F (38

°

C)

85

°

F (29

°

C)

Minimum Entering Air

1

50

°

F (10

°

C)

40

°

F (4

°

C)

Rated Entering Air

80/67

°

F (27

°

/19

°

C)

70

°

F (21

°

C)

Maximum Entering Air

2

100/83

°

F (38/28

°

C)

80

°

F (27

°

C)

Table 5: Fluid limits

Fluid Limits

Cooling

Heating

Minimum Entering

30°F (-1°C)

20°F (-6°C)

Normal Entering

77°F (25°C)

40°F (4°C)

Maximum Entering

110°F (43°C)

90°F (32°C)

Minimum GPM/Ton

1.5

Nominal GPM/Ton

3.0

Maximum GPM/Ton

4.0

Notes: 

1.  Maximum and minimum values may not be 

combined. If one value is at maximum or 

minimum, the other two conditions may not 

exceed the normal condition for standard 

units. Extended range unit may combine any 

two maximum conditions, but not more than 

two, with all other conditions being normal 

conditions.

 

2.  This is not a normal or continuous operating 

condition. It is assumed that such a start-up 

is for the purpose of bringing the building 

space up to occupancy temperature.

Electrical Data

General 

1. 

Be sure the available power is the same voltage 

and volt operation unless specified for 230 volts. 

phase as that shown on the unit serial plate. Line 

and voltage wiring must be done in accordance 

with local codes or the National Electrical Code, 

whichever is applicable.

2. 

Apply correct line voltage to the unit. A disconnect 

switch near the unit is required by code. Power 

to the unit must be sized correctly and have dual 

element (Class RK5) fuses or HACR circuit breaker 

for branch circuit overcurrent protection. See the 

nameplate for correct ratings.

3. 

All 208-230V single phase units are factory wired for 

208 volt operation unless specified for 230 volts.

Operating Voltages

115/60/1 ............................104 volts min.; 127 volts max.
208-230/60/1 ....................197 volts min.; 253 volts max.
265/60/1............................238 volts min.; 292 volts max.
230/50/1............................197 volts min.; 253 volts max.

Note: 

Voltages listed are to show voltage range. However, 

units operating circuit overcurrent protection. See the 

nameplate for with overvoltage or undervoltage for ex

-

tended periods of time will experience correct ratings. 

premature component failure.

www.DaikinApplied.com 13 

IM 447-11

Содержание WAA

Страница 1: ...els For Replacement of McQuay Console Models WAA WAF WAG WAH WAS WAX WCB WCQ WDA WDB WDC WDD WDE WDF WDG WDH WDJ WDL WDN WDS WDU WDX WDY WDZ WFQ WLA WLB WLC WLL WLZ WMA WMB WMC WMD WME WMF WMG WMH WMJ...

Страница 2: ......

Страница 3: ...lation 19 Multiple Unit Control Panel for Mark IV 20 Field Installed Outside Air Damper Accessory 21 Manual Outside Air Damper 21 Motorized Outside Air Damper 21 Motorized Outside Air Damper Wiring 22...

Страница 4: ...al Capacity 04 6 8 009 9 000 Btuh Nominal Cooling 012 12 000 Btuh Nominal Cooling 015 15 000 Btuh Nominal Cooling 019 19 000 Btuh Nominal Cooling Voltage 05 9 A 115 60 1 Size 009 and 012 only E 208 23...

Страница 5: ...WMO WMR WMS WMY WMZ WZS WZY 1 Field supplied control board 2 Subbase not included Physical Data Table 1 Physical Data Unit Size 009 012 015 019 Fan Wheel D x W in 5 3 4 x 9 15 5 3 4 x 9 15 6 x 7 8 6...

Страница 6: ...overed upon unpacking make a written request for inspection by the carrier s agent within fifteen 15 days of the delivery date and file a claim with the carrier Pre Installation WARNING The installer...

Страница 7: ...se STOP If an outside air damper kit is to be installed refer to Field Installed Outside Air Damper Acces sory on page 21 for the manual damper or the motorized damper kit and install it now 4 Positio...

Страница 8: ...ve a built in adjustable memory stop to eliminate rebalancing The valve installed on the return line acts as a balancing valve to adjust the proper water flow Each shutoff balancing valve has 1 2 FPT...

Страница 9: ...T 50 43 81 1 08 Condensate Hose Connection Each unit is supplied with a 3 4 19mm I D clear vinyl condensate hose internally trapped within the chassis The hose extends 14 356mm out of the chassis with...

Страница 10: ...itate removal for service Hard piping can also be brought directly to the unit although it is not recommended since additional noise 4 Some flexible hose threaded fittings are supplied with sealant co...

Страница 11: ...ater slightly alkaline pH 7 5 to 8 5 The specified percentage of antifreeze may also be added at this time Use commercial grade antifreeze designed for HVAC systems only Do not use automotive grade an...

Страница 12: ...Junction Box Figure 8 Cord plug connection field installed Power Cord Receptacle Plug Fuse Holder Switch Backwrap Fuse Disconnect Box 10 0 254mm 5 00 127mm Figure 9 Cabinet power connection field inst...

Страница 13: ...nimum the other two conditions may not exceed the normal condition for standard units Extended range unit may combine any two maximum conditions but not more than two with all other conditions being n...

Страница 14: ...A Min Volts Min Circuit Ampacity Max Fuse Size Volt Hz Phase kW Amps RLA LRA Nominal Actual 009 208 60 1 1 0 0 62 3 0 3 7 22 0 40 4 10 197 5 0 15 230 60 1 0 75 3 3 3 7 22 0 40 4 10 197 5 0 15 265 60 1...

Страница 15: ...itch is depressed the fan will run Cooling or Heating Auto Operation Rotate the thermostat knob to either warmer or cooler Select fan speed Depress the start button Unit will start within 0 to 32 seco...

Страница 16: ...ng shown below can only be used when the P terminal is not being used as a pump re start signal to other equipment If the P terminal must be used as a pump restart signal to other equipment then wire...

Страница 17: ...range yellow and white connections are short flying leads pre attached to the board The diagrams shown are some connection examples WSHP Mark IV AC Board Low Voltage Terminal Strip WSHP Mark IV AC Boa...

Страница 18: ...E L U A P V R C W1 Y1 W2 Y2 G Thermostat Terminals C R Non Programmable Auto or Manual Changeover Two Stage Heat Two Stage Cool Night Setback Override Dimensions Specifications Electrical Rating 24 VA...

Страница 19: ...2 Select an appropriate location for mounting the remote sensor 3 Mount remote sensor unit using hardware provided 4 Install two strand shielded wire between remote sensor and thermostat Shielded wir...

Страница 20: ...be used in combination with any other accessories or equipment that require VDC connections to the G W1 or Y1 terminals i e Boilerless System Kit The multiple unit control board provides the componen...

Страница 21: ...er Figure 19 Rear inlet typical motorized damper installation Backwrap Subbase 10 245mm Gasket Table 10 Dimensions in inches mm Unit Type Unit Size A B C Standard Height 009 012 46 1168 45 1143 25 635...

Страница 22: ...wires Damper Assembly Front View of Unit Subbase Chassis Gasket See Note 2 Screws See Note 1 Notes 1 Remove appropriate knock outs and install damper using two 2 8 18 screws provided 2 Install gasket...

Страница 23: ...operate properly perform troubleshooting as needed Troubleshooting Should a major problem develop refer to the following information for possible cause and corrective steps Neither fan nor compressor...

Страница 24: ...erant flow 5 Check for restriction in water flow Insufficient water flow through condenser 1 Check to see that valves are open all the way 2 Check for air in lines 3 Check circulating pump Water drips...

Страница 25: ...stle brush and a vacuum as neccessary 5 Inspect condensate drain lines twice per year and clean as needed to prevent build up lint and other particles that could cause overflow 6 Periodic lockouts alm...

Страница 26: ...ri mary wire and connecting the power lead to the orange transformer primary wire Place an insulation cap on the red transformer primary wire 2 All temperature and pressure switches are normally close...

Страница 27: ...ard 5 Transformer 6 Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 14 Terminal Board 1 15 Terminal Boar...

Страница 28: ...Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 13 Override Switch 14 Terminal Board 1 15 Terminal Boar...

Страница 29: ...sformer 6 Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 13 Override Switch 14 Terminal Board 1 15 Term...

Страница 30: ...lock 4 PC Board 5 Transformer 6 Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 14 Terminal Board 1 15 T...

Страница 31: ...mer 6 Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 13 Override Switch 14 Terminal Board 1 15 Terminal...

Страница 32: ...of Air ____________________________________________________________________ Filters Clean _____________________________________________________________________________ Condensate Traps Installed _____...

Страница 33: ...be converted to GPM by looking in the equipment specificaton catalog Caution P GPM Note A conversion table must be used to find GPM from Delta P measurements Loop Fluid Temperature Rise Drop through...

Страница 34: ...e 2 Model Serial H P EWT 3 LWT 4 EWP 1 LWP 2 EAT 5 LAT 6 Volts Amps Cool ing Check Air Filter and Coil Comments more comments on back 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25...

Страница 35: ...Notes Comments Form WS CTS 00 01 Rev 4 14 www DaikinApplied com 35 IM 447 11...

Страница 36: ...ent Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including To find your local Daikin Applied Representative go to www DaikinApplied com Aftermarket Servi...

Отзывы: