background image

Figure 2: Chassis (Left-hand slope top unit shown)

9.0"

(229mm)

Control Diagram

Compressor/Control Box

Access Cover

Escutcheon Plate

Wiring Diagram

Fan/Coil Section Access Panel

Condensate Line–14" (356mm) Clear Vinyl

Hose Clamp

Air Coil

Water Return

W

ater Supply

Junction Box

Flexible Hoses

Ball Valves

Electric Conduit

5.0"

(127mm)

All Pipe Fittings Are To Be

Field Installed

Water Connections

 All piping connections should be made using good 

plumbing practices and in accordance with any and all 

local codes that may apply. 

Note: 

It will be helpful to read, “Piping” on page

 

10

 

Unit Piping Connection 

Each heat pump is supplied with extended copper tubing 

on the water-to-refrigerant coil and 1/2" (12.7mm) OD 

tubing. The connections are for both the supply and 

return water connections. 

Note: Valves – Shut off Combination Balancing Valves, 

Hoses

 – Supply Return, Condensate Drain Hose and 

90

º

 Elbows are all factory available as accessories, (to 

be mounted in the field by others). 

Shutoff/Balancing Valve 

Each heat pump requires a shutoff valve on both the 

supply and return lines for easy serviceability and 

removal if it becomes necessary. 
We suggest using our combination shutoff/balancing 

valves installed in the field between the contractor’s 

piping and the heat pump unit. Constructed of brass 

and rated at 400 psig (2758 kPa) maximum working 

pressure. Valves have a built-in adjustable memory 

stop to eliminate rebalancing. The valve installed on the 

return line acts as a balancing valve to adjust the proper 

water flow. Each shutoff/balancing valve has 1/2" FPT × 

1/2" FPT threaded connections. 

Suggested Hose Kit Installation 

Field installed piping can be brought up from the floor or 

through the wall.

Notes: 

1.  Hoses are available in multiple lengths to 

acommodate various piping locations and 

optional components.

 

2

Make sure the pipes fit the confines of the 

piping compartment of the heat pump unit. 

See Figure 4 on page 

9.

 

Attach the field installed combination shut/off balancing 

valve to the building water supply and return piping. Next 

add the female pipe adapter connection to unit supply 

and return coil connection by sweating them in place 

using silver solder. 
Next, using the specified hose kit, screw the fixed 

end into the shut-off/balancing valve. Remove the 

1/2" adapter from the other end of the hose. Insert 

the adapter into the female fitting. Using two crescent 

wrenches, one to hold the pipe connection and the 

second to tighten the adapter, insert the swivel end of 

the hose on the adapter and tighten. This completes the 

hose connection to standard heat pump equipment.

Adding Motorized & Valve Assemblies 

All console water source heat pumps can be field 

installed with a motorized valve. All valves are mounted 

on the return line of each unit. All valve assemblies 

terminate with 1/2" NPT threaded connections and will 

also accommodate factory supplied hose kits.

IM 447-11 

www.DaikinApplied.com

Содержание WAA

Страница 1: ...els For Replacement of McQuay Console Models WAA WAF WAG WAH WAS WAX WCB WCQ WDA WDB WDC WDD WDE WDF WDG WDH WDJ WDL WDN WDS WDU WDX WDY WDZ WFQ WLA WLB WLC WLL WLZ WMA WMB WMC WMD WME WMF WMG WMH WMJ...

Страница 2: ......

Страница 3: ...lation 19 Multiple Unit Control Panel for Mark IV 20 Field Installed Outside Air Damper Accessory 21 Manual Outside Air Damper 21 Motorized Outside Air Damper 21 Motorized Outside Air Damper Wiring 22...

Страница 4: ...al Capacity 04 6 8 009 9 000 Btuh Nominal Cooling 012 12 000 Btuh Nominal Cooling 015 15 000 Btuh Nominal Cooling 019 19 000 Btuh Nominal Cooling Voltage 05 9 A 115 60 1 Size 009 and 012 only E 208 23...

Страница 5: ...WMO WMR WMS WMY WMZ WZS WZY 1 Field supplied control board 2 Subbase not included Physical Data Table 1 Physical Data Unit Size 009 012 015 019 Fan Wheel D x W in 5 3 4 x 9 15 5 3 4 x 9 15 6 x 7 8 6...

Страница 6: ...overed upon unpacking make a written request for inspection by the carrier s agent within fifteen 15 days of the delivery date and file a claim with the carrier Pre Installation WARNING The installer...

Страница 7: ...se STOP If an outside air damper kit is to be installed refer to Field Installed Outside Air Damper Acces sory on page 21 for the manual damper or the motorized damper kit and install it now 4 Positio...

Страница 8: ...ve a built in adjustable memory stop to eliminate rebalancing The valve installed on the return line acts as a balancing valve to adjust the proper water flow Each shutoff balancing valve has 1 2 FPT...

Страница 9: ...T 50 43 81 1 08 Condensate Hose Connection Each unit is supplied with a 3 4 19mm I D clear vinyl condensate hose internally trapped within the chassis The hose extends 14 356mm out of the chassis with...

Страница 10: ...itate removal for service Hard piping can also be brought directly to the unit although it is not recommended since additional noise 4 Some flexible hose threaded fittings are supplied with sealant co...

Страница 11: ...ater slightly alkaline pH 7 5 to 8 5 The specified percentage of antifreeze may also be added at this time Use commercial grade antifreeze designed for HVAC systems only Do not use automotive grade an...

Страница 12: ...Junction Box Figure 8 Cord plug connection field installed Power Cord Receptacle Plug Fuse Holder Switch Backwrap Fuse Disconnect Box 10 0 254mm 5 00 127mm Figure 9 Cabinet power connection field inst...

Страница 13: ...nimum the other two conditions may not exceed the normal condition for standard units Extended range unit may combine any two maximum conditions but not more than two with all other conditions being n...

Страница 14: ...A Min Volts Min Circuit Ampacity Max Fuse Size Volt Hz Phase kW Amps RLA LRA Nominal Actual 009 208 60 1 1 0 0 62 3 0 3 7 22 0 40 4 10 197 5 0 15 230 60 1 0 75 3 3 3 7 22 0 40 4 10 197 5 0 15 265 60 1...

Страница 15: ...itch is depressed the fan will run Cooling or Heating Auto Operation Rotate the thermostat knob to either warmer or cooler Select fan speed Depress the start button Unit will start within 0 to 32 seco...

Страница 16: ...ng shown below can only be used when the P terminal is not being used as a pump re start signal to other equipment If the P terminal must be used as a pump restart signal to other equipment then wire...

Страница 17: ...range yellow and white connections are short flying leads pre attached to the board The diagrams shown are some connection examples WSHP Mark IV AC Board Low Voltage Terminal Strip WSHP Mark IV AC Boa...

Страница 18: ...E L U A P V R C W1 Y1 W2 Y2 G Thermostat Terminals C R Non Programmable Auto or Manual Changeover Two Stage Heat Two Stage Cool Night Setback Override Dimensions Specifications Electrical Rating 24 VA...

Страница 19: ...2 Select an appropriate location for mounting the remote sensor 3 Mount remote sensor unit using hardware provided 4 Install two strand shielded wire between remote sensor and thermostat Shielded wir...

Страница 20: ...be used in combination with any other accessories or equipment that require VDC connections to the G W1 or Y1 terminals i e Boilerless System Kit The multiple unit control board provides the componen...

Страница 21: ...er Figure 19 Rear inlet typical motorized damper installation Backwrap Subbase 10 245mm Gasket Table 10 Dimensions in inches mm Unit Type Unit Size A B C Standard Height 009 012 46 1168 45 1143 25 635...

Страница 22: ...wires Damper Assembly Front View of Unit Subbase Chassis Gasket See Note 2 Screws See Note 1 Notes 1 Remove appropriate knock outs and install damper using two 2 8 18 screws provided 2 Install gasket...

Страница 23: ...operate properly perform troubleshooting as needed Troubleshooting Should a major problem develop refer to the following information for possible cause and corrective steps Neither fan nor compressor...

Страница 24: ...erant flow 5 Check for restriction in water flow Insufficient water flow through condenser 1 Check to see that valves are open all the way 2 Check for air in lines 3 Check circulating pump Water drips...

Страница 25: ...stle brush and a vacuum as neccessary 5 Inspect condensate drain lines twice per year and clean as needed to prevent build up lint and other particles that could cause overflow 6 Periodic lockouts alm...

Страница 26: ...ri mary wire and connecting the power lead to the orange transformer primary wire Place an insulation cap on the red transformer primary wire 2 All temperature and pressure switches are normally close...

Страница 27: ...ard 5 Transformer 6 Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 14 Terminal Board 1 15 Terminal Boar...

Страница 28: ...Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 13 Override Switch 14 Terminal Board 1 15 Terminal Boar...

Страница 29: ...sformer 6 Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 13 Override Switch 14 Terminal Board 1 15 Term...

Страница 30: ...lock 4 PC Board 5 Transformer 6 Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 14 Terminal Board 1 15 T...

Страница 31: ...mer 6 Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 13 Override Switch 14 Terminal Board 1 15 Terminal...

Страница 32: ...of Air ____________________________________________________________________ Filters Clean _____________________________________________________________________________ Condensate Traps Installed _____...

Страница 33: ...be converted to GPM by looking in the equipment specificaton catalog Caution P GPM Note A conversion table must be used to find GPM from Delta P measurements Loop Fluid Temperature Rise Drop through...

Страница 34: ...e 2 Model Serial H P EWT 3 LWT 4 EWP 1 LWP 2 EAT 5 LAT 6 Volts Amps Cool ing Check Air Filter and Coil Comments more comments on back 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25...

Страница 35: ...Notes Comments Form WS CTS 00 01 Rev 4 14 www DaikinApplied com 35 IM 447 11...

Страница 36: ...ent Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including To find your local Daikin Applied Representative go to www DaikinApplied com Aftermarket Servi...

Отзывы: