background image

Unit Location 

1. 

Console water source heat pumps are designed to 

be installed in a controlled environment. 

2. 

All units are to be installed against a wall. 

3. 

Each unit should be located on the architectural 

plans. The supply, return, and condensation piping 

should be located accordingly, making sure the 

piping will fit into the confines of the subbase and 

cabinet. 

Installing the Unit

  WARNING

Installation  and  maintenance  are  to  be  performed  by  qualified 
personnel who are familiar with local codes and Regulations, and 
experienced with this type of equipment.

 CAUTION

Sharp edges can cause personal injury. Avoid contact with them.

1. 

Consult job blueprints for unit location. Clean 

area where unit is to be installed, removing all 

construction dirt and debris. 

IMPORTANT

Clean unit mounting area of all construction debris. Check that 
the floor is level and at 90 degrees to the wall. Daikin McQuay 
recommends the placement of a sound absorbing mat beneath 
the unit footprint before continuing to the next installation step.

2. 

Remove unit from shipping carton and save the 

carton. Remove the front panel by removing a screw 

on each end of the cabinet. Lift the cabinet up, 

forward and off. 

3. 

Each chassis is mounted to cabinet backwrap and 

subbase assembly by six screws for shipment. 

Remove four screws, two on each side of the 

chassis at the subbase.

STOP! 

If an outside air damper kit is to be installed, refer 

to “Field Installed Outside Air Damper (Acces-

sory)” on page 

21

 for the manual damper or 

the motorized damper kit and install it now.

4. 

Position cabinet backwrap and subbase against the 

wall where unit is to be installed. Ensure adequate 

room exists for piping and electrical connection in 

the subbase by checking the connection end of the 

subbase. 

5. 

Using a carpenter’s square and level, make sure 

unit is level and that it is at a 90-degree angle with 

the wall and floor. 

Note: 

If the floor and wall are not at right angles, it will 

be necessary to shim the subbase for proper 

installation. Daikin will not accept responsibility 

for units that may need to be shimmed. Poor or 

inadequate installation could create noisy unit 

operation.

6. 

The cabinet backwrap has slots on the back 

flange to mount the assembly to the wall. It is the 

contractor’s responsibility to select the correct 

fastener for each unit, using a minimum of three (3) 

fasteners, Figure 1.

7. 

After securing the subbase and backwrap assembly 

in place, insert the chassis if it has been removed. 

Next, the electrical connection should be made, 

Figure 2 on page 

8

Figure 1: Cabinet backwrap & subbase

Subbase

Backwrap

10.0"*

(245mm)

A

C

B

Table 2: Dimensions in inches (mm)

Unit Type

Unit Size

A

B

C

Standard 

Height

009-012

46 (1168)

45 (1143)

25 (635)

015-019

54 (1372)

53 (1346)

25 (635)

Note: 

*Total unit is 10-3/4″ (273mm) deep. The cabinet extends beyond the  

subbase 1/4″ (6mm) in the back and 1/2″ (14mm) in the front.

www.DaikinApplied.com 

IM 447-11

Содержание WAA

Страница 1: ...els For Replacement of McQuay Console Models WAA WAF WAG WAH WAS WAX WCB WCQ WDA WDB WDC WDD WDE WDF WDG WDH WDJ WDL WDN WDS WDU WDX WDY WDZ WFQ WLA WLB WLC WLL WLZ WMA WMB WMC WMD WME WMF WMG WMH WMJ...

Страница 2: ......

Страница 3: ...lation 19 Multiple Unit Control Panel for Mark IV 20 Field Installed Outside Air Damper Accessory 21 Manual Outside Air Damper 21 Motorized Outside Air Damper 21 Motorized Outside Air Damper Wiring 22...

Страница 4: ...al Capacity 04 6 8 009 9 000 Btuh Nominal Cooling 012 12 000 Btuh Nominal Cooling 015 15 000 Btuh Nominal Cooling 019 19 000 Btuh Nominal Cooling Voltage 05 9 A 115 60 1 Size 009 and 012 only E 208 23...

Страница 5: ...WMO WMR WMS WMY WMZ WZS WZY 1 Field supplied control board 2 Subbase not included Physical Data Table 1 Physical Data Unit Size 009 012 015 019 Fan Wheel D x W in 5 3 4 x 9 15 5 3 4 x 9 15 6 x 7 8 6...

Страница 6: ...overed upon unpacking make a written request for inspection by the carrier s agent within fifteen 15 days of the delivery date and file a claim with the carrier Pre Installation WARNING The installer...

Страница 7: ...se STOP If an outside air damper kit is to be installed refer to Field Installed Outside Air Damper Acces sory on page 21 for the manual damper or the motorized damper kit and install it now 4 Positio...

Страница 8: ...ve a built in adjustable memory stop to eliminate rebalancing The valve installed on the return line acts as a balancing valve to adjust the proper water flow Each shutoff balancing valve has 1 2 FPT...

Страница 9: ...T 50 43 81 1 08 Condensate Hose Connection Each unit is supplied with a 3 4 19mm I D clear vinyl condensate hose internally trapped within the chassis The hose extends 14 356mm out of the chassis with...

Страница 10: ...itate removal for service Hard piping can also be brought directly to the unit although it is not recommended since additional noise 4 Some flexible hose threaded fittings are supplied with sealant co...

Страница 11: ...ater slightly alkaline pH 7 5 to 8 5 The specified percentage of antifreeze may also be added at this time Use commercial grade antifreeze designed for HVAC systems only Do not use automotive grade an...

Страница 12: ...Junction Box Figure 8 Cord plug connection field installed Power Cord Receptacle Plug Fuse Holder Switch Backwrap Fuse Disconnect Box 10 0 254mm 5 00 127mm Figure 9 Cabinet power connection field inst...

Страница 13: ...nimum the other two conditions may not exceed the normal condition for standard units Extended range unit may combine any two maximum conditions but not more than two with all other conditions being n...

Страница 14: ...A Min Volts Min Circuit Ampacity Max Fuse Size Volt Hz Phase kW Amps RLA LRA Nominal Actual 009 208 60 1 1 0 0 62 3 0 3 7 22 0 40 4 10 197 5 0 15 230 60 1 0 75 3 3 3 7 22 0 40 4 10 197 5 0 15 265 60 1...

Страница 15: ...itch is depressed the fan will run Cooling or Heating Auto Operation Rotate the thermostat knob to either warmer or cooler Select fan speed Depress the start button Unit will start within 0 to 32 seco...

Страница 16: ...ng shown below can only be used when the P terminal is not being used as a pump re start signal to other equipment If the P terminal must be used as a pump restart signal to other equipment then wire...

Страница 17: ...range yellow and white connections are short flying leads pre attached to the board The diagrams shown are some connection examples WSHP Mark IV AC Board Low Voltage Terminal Strip WSHP Mark IV AC Boa...

Страница 18: ...E L U A P V R C W1 Y1 W2 Y2 G Thermostat Terminals C R Non Programmable Auto or Manual Changeover Two Stage Heat Two Stage Cool Night Setback Override Dimensions Specifications Electrical Rating 24 VA...

Страница 19: ...2 Select an appropriate location for mounting the remote sensor 3 Mount remote sensor unit using hardware provided 4 Install two strand shielded wire between remote sensor and thermostat Shielded wir...

Страница 20: ...be used in combination with any other accessories or equipment that require VDC connections to the G W1 or Y1 terminals i e Boilerless System Kit The multiple unit control board provides the componen...

Страница 21: ...er Figure 19 Rear inlet typical motorized damper installation Backwrap Subbase 10 245mm Gasket Table 10 Dimensions in inches mm Unit Type Unit Size A B C Standard Height 009 012 46 1168 45 1143 25 635...

Страница 22: ...wires Damper Assembly Front View of Unit Subbase Chassis Gasket See Note 2 Screws See Note 1 Notes 1 Remove appropriate knock outs and install damper using two 2 8 18 screws provided 2 Install gasket...

Страница 23: ...operate properly perform troubleshooting as needed Troubleshooting Should a major problem develop refer to the following information for possible cause and corrective steps Neither fan nor compressor...

Страница 24: ...erant flow 5 Check for restriction in water flow Insufficient water flow through condenser 1 Check to see that valves are open all the way 2 Check for air in lines 3 Check circulating pump Water drips...

Страница 25: ...stle brush and a vacuum as neccessary 5 Inspect condensate drain lines twice per year and clean as needed to prevent build up lint and other particles that could cause overflow 6 Periodic lockouts alm...

Страница 26: ...ri mary wire and connecting the power lead to the orange transformer primary wire Place an insulation cap on the red transformer primary wire 2 All temperature and pressure switches are normally close...

Страница 27: ...ard 5 Transformer 6 Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 14 Terminal Board 1 15 Terminal Boar...

Страница 28: ...Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 13 Override Switch 14 Terminal Board 1 15 Terminal Boar...

Страница 29: ...sformer 6 Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 13 Override Switch 14 Terminal Board 1 15 Term...

Страница 30: ...lock 4 PC Board 5 Transformer 6 Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 14 Terminal Board 1 15 T...

Страница 31: ...mer 6 Boilerless Relay 7 Shutdown Relay 8 Auxiliary Relay 9 Heater Relay 10 Water Reg Valve Relay 11 Low Limit Thermostat 12 Night Setback Thermostat 13 Override Switch 14 Terminal Board 1 15 Terminal...

Страница 32: ...of Air ____________________________________________________________________ Filters Clean _____________________________________________________________________________ Condensate Traps Installed _____...

Страница 33: ...be converted to GPM by looking in the equipment specificaton catalog Caution P GPM Note A conversion table must be used to find GPM from Delta P measurements Loop Fluid Temperature Rise Drop through...

Страница 34: ...e 2 Model Serial H P EWT 3 LWT 4 EWP 1 LWP 2 EAT 5 LAT 6 Volts Amps Cool ing Check Air Filter and Coil Comments more comments on back 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25...

Страница 35: ...Notes Comments Form WS CTS 00 01 Rev 4 14 www DaikinApplied com 35 IM 447 11...

Страница 36: ...ent Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including To find your local Daikin Applied Representative go to www DaikinApplied com Aftermarket Servi...

Отзывы: