t
ypiCal
W
iring
d
iagraMs
Typical Mark IV/AC
Fan
Motor
070 - Blk
060 - Blk
048 - Red
042 - Blk
036 - Blk
030 - Blk
Compr
Motor
CC - Compressor Contactor
HTR - Crankcase Heater (Optional)
CAP
- Motor Capacitor
Condensate
Sensor
Common Fan
L1
Compressor
Reversing Valve
Solenoid (24 VAC)
0 W
2
G W
1
Y
1 F E L U A P V R C
Mark IV
PC
Board
Hi Pressure
Lo Pressure
Lo
Te
mp
Ground
L1
L2
CC
Heater
Component Layout
1 Compressor Contactor
2 Fan Contactor
3 Transformer
4 PC Board
5 Auxiliary Relay
6 Circuit Breaker
Notes:
1.
Unit is factory wired for 208V operation. If 230V power supply is used, transformer must be rewired by disconnecting the power lead from the red transformerpri-
mary wire and connecting the power lead to the orange transformer primary wire. Place an insulation cap on the red transformer primary wire.
2.
All temperature and pressure switches are normally closed.
3.
Component layout shown below is typical. Some components may not be used on this model or voltage.
4.
Mark IV/AC controller board contains a static sensitive microprocessor. Proper grounding of field service personnel should be observed or damage to controller
may result.
5.
Terminal block on Mark IV/AC board provides 24 VAC at terminals R and C. All other outputs are 24 VDC.
6.
Field supplied relays installed on the input terminals (W1, W2, Y1 or G) may interfere with proper unit operation. Never install relay coils in series with inputs.
7.
For more information pertaining to the Mark IV/AC controller, refer to OM120.
IM 447-11
26 www.DaikinApplied.com
Содержание WAA
Страница 2: ......
Страница 35: ...Notes Comments Form WS CTS 00 01 Rev 4 14 www DaikinApplied com 35 IM 447 11...