7
|
Configuration
Installer and user reference guide
93
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10
[2‑9]
T
c
target (°C)
6
46
For more information and advice about the impact of these settings, see
"7.3 Energy saving and optimum operation"
[2‑12]
Enable the low noise function and/or power consumption limitation via external
control adaptor (DTA104A61/62).
If the system needs to be running under low noise operation or under power
consumption limitation conditions when an external signal is sent to the unit, this
setting should be changed. This setting will only be effective when the optional
external control adaptor (DTA104A61/62) is installed.
[2‑12]
Description
0 (default)
Deactivated.
1
Activated.
[2‑14]
Input additional refrigerant amount that was charged.
In case you want to use the automatic leak detection functionality, it is required to
input the total additional refrigerant charge amount.
[2‑14]
Additional amount charged (kg)
0 (default)
No input
1
0<x<5
2
5<x<10
3
10<x<15
4
15<x<20
5
20<x<25
6
25<x<30
7
30<x<35
8
35<x<40
9
40<x<45
10
45<x<50
11
50<x<55
12
55<x<60
13
60<x<65
14
65<x<70
15
70<x<75
16
75<x<80
17
80<x<85
18
85<x<90
Содержание VRV IV+
Страница 165: ......
Страница 166: ......
Страница 167: ......
Страница 168: ...4P546228 1A 2019 10 Copyright 2018 Daikin Verantwortung für Energie und Umwelt ...